2020-12-08 14:24:44 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20120003 |
| ADD: 2400 S DIXIE HWY. |
| CONT: BUTLER CONSTRUCTION |
| TEL: 561-832-9700 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 08TH/2020 |
| ACTION: DENIED |
| |
| 1) MISSING CODE DATA NOT FOUND ON THE PLANS, NO LIFE |
| SAFETY SHEET. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| OR STRUCTURES. |
| 107.3.5.1 COMMERCIAL BUILDINGS |
| 107.3.5.1.1. BUILDING |
| |
| 1A) MISSING CODE DATA: |
| OCCUPANCY GROUP OLD AND PROPOSED NEW |
| CHANGE OF OCCUPANCIES FOR A WHOLE BUILDING WOULD |
| REQUIRE THE PLANS DESIGNED TO THE 2017 FBC-EXISTING |
| BUILDING CODE, CHAPTER 10, AND SECTION 1001.2.2, FOR A |
| FULL BUILDING. |
| |
| 1B) MINIMUM TYPE OF CONSTRUCTION SECTION 503 |
| FIRE SPRINKLERED OR NOT |
| FIRE RESISTANCE SEPARATION |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFT STOPPING AND CALCULATED FIRE |
| RESISTANCE |
| |
| 1C) FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| EARLY WARNING SMOKE EVACUATION SYSTEMS |
| SCHEMATIC FIRE SPRINKLERS |
| STANDPIPES |
| PRE-ENGINEERED SYSTEMS |
| RISER DIAGRAM |
| |
| 1D) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| CONSTRUCTION REQUIREMENTS |
| |
| 2) SHEET A002 SITE DETAILS / ACCESSIBLE STALL PARKING. |
| THE DETAIL DOES NOT MEET THE CITY STANDARD FOR |
| ACCESSIBLE PARKING SPACES, PLEASE REVIEW CITY OF W. P. |
| B. STANDARD LINES ARE 4 INCHES WIDE WITH 12 INCHES/ 1 |
| FOOT BETWEEN LINES. |
| ACCESSIBLE PARKING SPACE / STALL PAINTING. |
| |
| 2A) 2017 ACCESSIBILITY CODE SECTION 502.2 VEHICLE |
| SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET |
| WIDE, SHALL BE MARKED TO DEFINE THE WIDTH, AND SHALL |
| HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH 502.3. |
| ADVISORY 502.3.3MARKING THE METHOD AND MARKING OF COLOR |
| OF MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT |
| MAY BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS. |
| WEST PALM MUNI-CODE ARTICLE XV PARKING DETAIL, 94-485 |
| ILLUSTRATES WITH MEASUREMENTS FOR DOUBLE STRIPE STALL |
| PAINTING. |
| |
| 2B) IN THESE DETAILS THE ELEVATIONS ARE NOT GIVEN AT |
| THE CORNERS OF THE ACCESSIBLE PARKING SPACE AND |
| ADJACENT ACCESS AISLE. |
| 2017 FBC-ACCESSIBILITY CODE 502.4 ACCESS AISLE & |
| PARKING SPACE SAME LEVEL/ 502.4, FLOOR AND GROUND |
| SURFACES. PARKING SPACES AND THE ACCESS AISLES SERVING |
| THEM SHALL COMPLY WITH 302. ACCESS AISLES SHALL BE AT |
| THE SAME LEVEL AS THE PARKING SPACES THEY SERVE. |
| CHANGES IN LEVEL ARE NOT PERMITTED. EXCEPTION: SLOPES |
| NOT GREATER THAN 1:48 SHALL BE PERMITTED. |
| |
| 3) SHEET A101: |
| 3A) SHEET A101 IT IS ASSUMED TO BE THE PROPOSED LAYOUT |
| OF THE BASEMENT PLAN. NO LIFE SAFETY INFORMATION WAS |
| PROVIDED FOR THIS REVIEW. THE BASEMENT PLAN DOES NOT |
| SHOW THE COMMON PATH OF TRAVEL FROM THE FURTHEST POINT |
| TIN THE BASEMENT TO THE HEAD OF THE STAIRS AT WHICH YOU |
| HAVE 2 CHOICES OF EXIT TRAVEL, PLEASE SHOW COMPLIANCE |
| WITH THE 2017 FBC-B TABLE 1006.3.2(2). |
| |
| 3B) THERE IS NO INFORMATION ON THE STAIRWAY AND |
| HANDRAILS IF THEY ARE EXISTING AND THE RISE / RUN OF |
| THE STAIRS NOR IF THERE IS ANY HANDRAILS. SEE THE 2017 |
| FBC-EXISTING BUILDING CODE SECTION 1012.4.2. |
| |
| 4) SHEET A102 THE PROPOSED 1ST FLOOR PLAN: |
| 4A) THE PLANS DO NOT SHOW WHICH EGRESS DOORS ARE |
| ACCESSIBLE EXITS. 2017 FBC-ACCESSIBILITY CODE SECTION |
| 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION |
| 1003.2.13 OF THE INTERNATIONAL BUILDING CODE (2000 |
| EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF THE |
| INTERNATIONAL BUILDING CODE (2003 EDITION). |
| |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| |
| 4B) THE PLANS DO NOT SHOW COMPLIANCE WITH SECTION |
| 1007.1.1 OF THE 2017 FBC-B, TWO EXITS AND OR EXIT |
| ACCESS DOORWAYS. |
| WHERE 2 EXIT OR EXIT ACCESS DOORWAYS ARE REQUIRED FROM |
| ANY PORTION OF THE EXIT ACCESS, THEY SHALL BE PLACED A |
| DISTANCE APART EQUAL TO NOT LESS THAN ? THE OVERALL |
| MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| THEM. |
| EXCEPTION BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 903.3.1.1 OR 903.3.1.2, THE SEPARATION DISTANCE SHALL |
| NOT BE LESS THAN 1/3RD OVERALL DIAGONAL DIMENSION OF |
| THE BUILDING OR AREA TO BE SERVED MEASURED IN A |
| STRAIGHT LINE BETWEEN THEM. |
| |
| 4C) PLEASE REVIEW THE STAIRWAY THAT LEADS FORM THE |
| BASEMENT. THE 2017 FBC-B SECTION 1019.3 WOULD REQUIRE |
| THE STAIRWAY TO BE ENCLOSED WITH A SHAFT ENCLOSURE |
| CONSTRUCTED IN ACCORDANCE WITH 713. DOORS WILL NEED TO |
| SHOW COMPLIANCE WITH 713.7 & 716 FOR FIRE BARRIER. |
| DOORS SHALL BE SELF OR AUTOMATIC CLOSING BY SMOKE |
| DETECTION IN ACCORDANCE WITH 716.5.9.3. |
| |
| 4D)(1) THE PROPOSED FLOOR PLAN SHOWS A NEW 800 SQ. FT. |
| WALK IN COOLER. PLEASE NOTE WALK IN COOLERS REQUIRE A |
| SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. THEY ARE |
| ALSO PART OF THE COMPONENTS AND CLADDING OF THE |
| BUILDING AND REQUIRE PRODUCT APPROVALS. 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: (31)(G) EXTERIOR COOLER, FREEZERS |
| |
| 4D)(2) *00 SQ. FT. COOLERS WILL ALSO NEED TO SHOW |
| COMPLIANCE WITH THE 2017 FBC-B SECTION 2603.4.1.2 AND |
| 2603.4.1.3. |
| |
| 4E) THE PLAN INDICATES THERE IS 110 INDOOR SEATS. THE |
| FLOOR PLAN DOES NOT SHOW ANY ACCESSIBLE SEATING. PLEASE |
| SHOW COMPLIANCE WITH THE FOLLOWING ACCESSIBILITY |
| REQUIREMENTS: |
| |
| 4E)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| SEATING SPACES AND STANDING SPACES AT THE DINING |
| SURFACES SHALL COMPLY WITH 902. 110X0.05= 6SEATS. |
| |
| 4E)(2) 226.2 DISPERSION. DINING SURFACES AND WORK |
| SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| SURFACES AND WORK SURFACES. |
| |
| 4E)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN |
| RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL |
| BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR |
| SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| |
| 4E)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| COUNTERS, AND WHERE COVERED BY THE ADA SCOPING |
| PROVISIONS, EMPLOYEE WORKSTATIONS (CHECK-OUT COUNTERS). |
| |
| 4E)(5)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR |
| FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| COMPLYING WITH 306 SHALL BE PROVIDED. |
| |
| 4E)(5)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 4F) PLEASE LOOK AT DOORS 12 & 13 MISSING MANEUVERING |
| CLEARANCES AT DOORS. ACCESS. CODE 404.2.4 MANEUVERING |
| CLEARANCES. DOORS. |
| MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| LATCH SIDE FOR SIDE CLEARANCE. |
| |
| 4G) PLEASE NOTE THE EXTERIOR DOOR LOCATED BY THE HAND |
| SINK AND OLE HICKORY IS A INSWING DOOR THE OCCUPANT |
| LOAD OF THE BUILDING IS WELL OVER 50. 2017 FBC-B |
| 1010.1.2.1. DIRECTION OF SWING. PIOT OR SIDE-HINGED |
| SWINGING DOORS SHALL SWING IN THE DIRECTION OF EGRESS |
| TRAVEL WHERE SERVING ROOMS OR AREAS CONTAINING AN |
| OCCUPANT LOAD OF 50 OR MORE. |
| |
| 5) SHEET A104 ENLARGES RESTROOM FLOOR PLAN & |
| ELEVATIONS: |
| 5A) THERE IS NO FINISHES SHEET FOR FLOORS, WALLS & |
| CEILINGS. SHEET A104 IN THE SOUTH ELEVATION OF THE MENS |
| RESTROOM STATES LINE OF SMOOTH, HARD, NONABSORBENT |
| SURFACES ABOVE THE FLOOR. 2017 FBC-B 1210.2.2. WALLS & |
| PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO |
| LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| |
| 5A)(1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| |
| 5A)(2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET |
| WALLS SHALL COMPLY WITH 1210.2. |
| |
| 5A)(3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS |
| AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY |
| WITH SECTIONS 1210.1 THROUGH 1210.4. |
| |
| 5B) WITHIN THE LADIES RESTROOM WHEN THE BABY CHANGING |
| TABLE IS IN THE DOWN POSITION YOU DO NOT HAVE THE |
| MANEUVERING CLEARANCES AT DOOR # 07. ACCESS. CODE |
| 404.2.4 MANEUVERING CLEARANCES. DOORS. |
| MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| LATCH SIDE FOR SIDE CLEARANCE. FIGURE 404.2.4.1(A). |
| |
| 5C) IN BOTH THE MENS AND WOMENS RESTROOMS THE HEIGHT |
| ABOVE THE FLOOR IS NOT GIVEN, SHOW COMPLIANCE WITH |
| 603.3 MIRRORS. 2017 FBC-ACCESSIBILITY CODE. MIRRORS |
| LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE |
| INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 5D) THE TOILET PAPER DISPENSER DOES NOT COMPLY WITH THE |
| DISTANCE FROM THE FRONT OF THE WATER CLOSET. TOILET |
| PAPER DISPENSERS. 604.7. THE TOILET PAPER DISPENSER |
| SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| MEASURED TO THE CENTERLINE OF THE DISPENSER. |
| |
| 5E) THE ELEVATIONS FOR BOTH THE MENS AND LADIES |
| RESTROOMS DEPICT THE GRAB BARS DIMENSIONED FROM THE |
| CENTER LINE. PLEASE NOTE THE 2017 FBC-ACCESSIBILITY |
| CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS |
| SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT |
| CENTERLINE. |
| |
| 5F) THE ELEVATIONS FOR BOTH THE MENS AND LADIES |
| RESTROOMS DEPICT THE LAVATORY WITH A PROTECTION BOARD |
| FOR PREVENTING EXPOSED PIPES IN COMPLIANCE WITH 606.5. |
| WHAT IS MISSING FROM THE DETAIL IS COMPLIANCE WITH |
| 306.2 CLEARANCES FOR TOES AND 306.3 CLEARANCES FOR |
| KNEES. |
| |
| 5G) WHAT DETAILS FOR ACCESSIBILITY WERE NOT PROVIDED |
| AND OR EXCEPTION ARE FOR DRINKING FOUNTAINS. |
| 5G)(1) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| PROVIDED. |
| |
| 5G)(2) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| |
| 5G)(3) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS |
| 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES |
| AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT |
| PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE |
| CIRCULATION PATH. |
| |
| 6) SHEET S101 THE ROOF FRAMING PLAN. THE WIND DESIGN |
| CRITERIA ARE GIVEN ON THIS PLAN WHAT IS MISSING IS THE |
| MEAN ROOF HEIGHT. WIND EXPOSURE. APPLICABLE WIND |
| DIRECTION IF MORE THAN ONE WIND EXPOSURE IS UTILIZED. |
| TABLE 1609.7.2. HEIGHT AND EXPOSURE. ASCE 7-10 TABLE |
| 30.3.1. THE ELEVATIONS ON THE 200 SERIES OF DRAWINGS |
| SHOWS THE ROOF AT 29.0 + PARAPET APPROX.. 30 FEET. |
| |
| 7) THE COMPONENT AND CLADDING PRESSURES FOUND ON S302 |
| FOR THE ROOF AND WALL ZONES ARE GIVEN IN VASD. THANK |
| YOU. THE WALL PRESSURES ARE UP TO 9.0 LBS. LOW PER PSF. |
| WE ARE TAKING THE PRESSURES FROM AN ENGINEERS SPREAD |
| SHEET FOR WALL COMPONENTS & CLADDING AND COMPARING TO |
| ASCE 7-10 FIGURE 30.5.1, AS WELL AS THE PRESSURES FOUND |
| IN THE 2017 RESIDENTIAL CODE THE SIMPLIFIED TABLE |
| R301.2(2). |
| |
| 8) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE |
| WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED. |
| REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF |
| FRAMING INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| 1. WELD PROCEDURES SPECIFICATIONS |
| 2. QUALIFICATIONS OF WELDING PERSONAL |
| 2017 FBC-B 2204.2 BOLTING. |
| IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| AT 561-805-6666. |
| |
| 9) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS. |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP CURBS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 10) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 12) THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE |
| REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| |
| 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 14) 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS |
| OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING |
| ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED |
| STRUCTURE OR THE ROOF OF A BUILDING SUCH THAT PERSONNEL |
| WILL HAVE TO CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE |
| GRADE TO ACCESS SUCH EQUIPMENT OR APPLIANCES, AN |
| INTERIOR OR EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. |
| SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER |
| OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) IN HEIGHT |
| OR WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS |
| VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE). |
| SUCH ACCESS SHALL NOT REQUIRE THE USE OF PORTABLE |
| LADDERS. WHERE ACCESS INVOLVES CLIMBING OVER PARAPET |
| WALLS, THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE |
| PARAPET WALL. |
| |
| 15) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| |
| 16) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |