| REVIEW STATUS: FAILED. |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| 1) NO ELECTRICAL DETAILS PROVIDED. PLEASE INCLUDE A |
| RISER DIAGRAM SHOWING SIZE OF ELECTRICAL SERVICE, WIRE |
| SIZE AND GROUNDING DETAILS. |
| 2) PLEASE INCLUDE DETAIL SHOWING COMPLIANCE WITH NEC |
| 300.5, INCLUDING UNDERGROUND RATED CONDUIT/CASING, |
| DEPTH OF COVER, DISTANCE FROM POOL, ETC. |
| 3) UNDERGROUND INSTALLATION MUST COMPLY WITH NEC 680.10 |
| 4) DRAWING MUST HAVE NAME AND SIGNATURE OR CONTRACTOR |
| QUALIFIER. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |