2020-11-25 12:46:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET SITE PLAN - THE OCCUPANCY LOAD CALUCLATION |
| DOES NOT APPEAR TO MEET THE REQUIRMENTS OF NFPA 101, CH |
| 7 |
| |
| 13,237 SQ FT OF AN ASSEMBLY OCCUPANCY IS PER TABLE |
| 7.3.1.2 AT 15 SQ FT/ PERSON. P OR 889 |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 1A) THERE ARE INDICATIONS OF STAIRS LEADING FROM EACH |
| AREA AS A PART OF THE EGRESS PATH TO A PUBLIC WAY. |
| |
| THE CAPACITY AND CLACULATION OF STAIRS WITHIN AN EXIT |
| TRAVLE PATH ARE CALCULATED DIFFERENT AND SEPARATE OF A |
| SIMPLE EXIT OPENING. |
| |
| PER TABLE 7.3.3.1 - .3 IS THE REQUIRED FACTOR |
| |
| PLEASE CORRECT. |
| |
| |
| |
| 1B) BASED ON THE ABOVE THERE ARE INSUFFICIENT EGRESS |
| CAPACITY TO ACCOMDATE THE REQUIREMENT. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 2) THERE IS AN INDICATION A FIRE SPRINKLERS AND A |
| STATEMENT " AND SHALL HAS A FIRE ALARM SYSTEM" |
| |
| PLEASE DEFINE THIS STATEMENT AND PROVIDE WHAT TYPE OF |
| FIRE ALARM IS EXISTING OR WILL BE PROVIDED. |
| |
| WHAT KIND/TYPE/LOCATION OF NOTIFICATION DEVICES ARE |
| WITHIN THE PROPOSED AREA? |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| 2A) ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 3) EXIT DOORS ARE INDICATED; HOWEVER, THERE ARE NO |
| INDICATIONS OF THE EXIT HARDWARE TYPE. |
| |
| PANIC HARDWARE IS REQUIRED. |
| |
| PER NFPA 101, CH 12 ASSEMBLY OCCUPANCIES |
| |
| 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| AN AREA HAVING |
| AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| PERMITTED TO BE |
| PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK |
| IS PANIC |
| HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, |
| UNLESS |
| OTHERWISE PERMITTED BY ONE OF THE FOLLOWING |
| (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS |
| LOCKS AS |
| PERMITTED IN 12.2.2.2.5. |
| (2) THIS REQUIREMENT SHALL NOT APPLY TO |
| ACCESS-CONTROLLED EGRESS DOORS |
| AS PERMITTED IN 12.2.2.2.6. |
| 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 |
| SHALL BE PERMITTED |
| TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS |
| IF BOTH OF THE |
| FOLLOWING CONDITIONS APPLY: |
| (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT |
| AND THE ASSEMBLY |
| OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. |
| (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN |
| ASSEMBLY |
| OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE |
| RELEASED |
| BY PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT. |
| |
| |
| |
| 4) PLEASE PROVIDE DETAILS OF WHAT KIND OF EVENT IS |
| PROPOSED. |
| |
| WILL THERE BE ANY PYROTECHICS/ OPEN FLAME EFFECTS, |
| ETC.? |
| |
| PLEASE PROVIDE DETAILS |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |