Plan Review Notes
Plan Review Notes For Permit 20111134
Permit Number 20111134
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-11-25 12:46:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET SITE PLAN - THE OCCUPANCY LOAD CALUCLATION
 DOES NOT APPEAR TO MEET THE REQUIRMENTS OF NFPA 101, CH
 7
  
 13,237 SQ FT OF AN ASSEMBLY OCCUPANCY IS PER TABLE
 7.3.1.2 AT 15 SQ FT/ PERSON. P OR 889
  
 PLEASE REVIEW AND CORRECT.
  
  
 1A) THERE ARE INDICATIONS OF STAIRS LEADING FROM EACH
 AREA AS A PART OF THE EGRESS PATH TO A PUBLIC WAY.
  
 THE CAPACITY AND CLACULATION OF STAIRS WITHIN AN EXIT
 TRAVLE PATH ARE CALCULATED DIFFERENT AND SEPARATE OF A
 SIMPLE EXIT OPENING.
  
 PER TABLE 7.3.3.1 - .3 IS THE REQUIRED FACTOR
  
 PLEASE CORRECT.
  
  
  
 1B) BASED ON THE ABOVE THERE ARE INSUFFICIENT EGRESS
 CAPACITY TO ACCOMDATE THE REQUIREMENT.
  
 PLEASE REVIEW AND CORRECT.
  
  
 2) THERE IS AN INDICATION A FIRE SPRINKLERS AND A
 STATEMENT " AND SHALL HAS A FIRE ALARM SYSTEM"
  
 PLEASE DEFINE THIS STATEMENT AND PROVIDE WHAT TYPE OF
 FIRE ALARM IS EXISTING OR WILL BE PROVIDED.
  
 WHAT KIND/TYPE/LOCATION OF NOTIFICATION DEVICES ARE
 WITHIN THE PROPOSED AREA?
  
 PLEASE PROVIDE DETAILS.
  
  
 2A) ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) EXIT DOORS ARE INDICATED; HOWEVER, THERE ARE NO
 INDICATIONS OF THE EXIT HARDWARE TYPE.
  
 PANIC HARDWARE IS REQUIRED.
  
 PER NFPA 101, CH 12 ASSEMBLY OCCUPANCIES
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE
 PROVIDED WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK
 IS PANIC
 HARDWARE OR FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7,
 UNLESS
 OTHERWISE PERMITTED BY ONE OF THE FOLLOWING
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 LOCKS AS
 PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO
 ACCESS-CONTROLLED EGRESS DOORS
 AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE
 FOLLOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY
 OCCUPANCY HAVING AN OCCUPANT LOAD OF 100 OR MORE ARE
 RELEASED
 BY PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT.
  
  
  
 4) PLEASE PROVIDE DETAILS OF WHAT KIND OF EVENT IS
 PROPOSED.
  
 WILL THERE BE ANY PYROTECHICS/ OPEN FLAME EFFECTS,
 ETC.?
  
 PLEASE PROVIDE DETAILS
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  