Plan Review Notes
Plan Review Notes For Permit 20111108
Permit Number 20111108
Review Stop P
Sequence Number 3
Notes
Date Text
2021-03-11 16:46:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20111108 514 14TH ST
 3RD REVIEW
  
 PLUMBING COMMENTS:DENIED
  
 NOTE: IN RECEIPT OF BIG WATER HEMP LOR 2 RESPONSE TO
 PLBG REVIEW 2 DATED 2/23/2021, FORWARDED BY EMAIL FROM
 KIMBERLY LEWIS OF SR CONSTRUCTION SERVICES LLC ON
 3/11/2021.
  
 PLEASE NOTE THAT PLAN SHEETS 014 P-2 PLUMBING ISOMETRIC
 DETAILS, 013 P-1 PLUMBING FLOOR PLAN-ENLAGED
 PLAN-TRENCH INFILLS AND 015 IRR-1 IRRIGATION
 PLAN-IRRIGATION ISOMETRIC-DETAILS HAVE BEEN REDLINED IN
 AN ATTEMPT TO HELP CLARIFY COMMENTS.
 COMMENTS FROM REVIEW DATED 2/23/2021.
  
 1) IRR-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COMPONENTS OF THE HYDROPONIC IRRIGATION SYSTEM
 INCLUDING THE REVERSE OSMOSIS TREATMENT SYSTEM, BOOSTER
 PUMP, WATER STORAGE TANKS, PIPING AND TUBING, AND THE
 ADDITIONAL COMPONENTS LISTED ON THE PLAN SHEET. PLEASE
 NOTE THE SPECS MAY BE DEFERRED SUBMITTALS TO PROVIDED
 AT A LATER DATE WITH THE ARCHITECT?S APPROVAL STAMP-
 SEE SECTIONS 107.1, 107.3, AND 107.3.4.1 WPB AMENDMENTS
 TO THE FBC-2017.
 PROVISO: SPECS MAY BE DEFERRED SUBMITTALS TO PROVIDED
 AT A LATER DATE WITH THE ARCHITECT?S APPROVAL STAMP-
 SEE SECTIONS 107.1, 107.3, AND 107.3.4.1 WPB AMENDMENTS
 TO THE FBC-17. PROCEED AT YOUR OWN RISK.
  
 2) PLEASE PROVIDE AN ITEMIZED BREAKDOWN OF COSTS
 ASSOCIATED WITH THE CHANGES IN THE PLANS AND PROJECTS
 INCLUDING THE IRRIGATION SYSTEM, ADDITIONAL TOILET
 ROOM, WATER HEATERS ETC.- SECTION 109.3 WPB.
 RESPONSE; TO BE PROVIDED BY GC.
 BREAKDOWN MUST BE PROVIDED AND APPROVED PRIOR TO
 APPROVAL FOR PERMIT.
  
 3) CLARIFY IF THE IRRIGATION SYSTEM WILL BE INSTALLED
 BY THE PLUMBING SUB-CONTRACTOR OR BY ANOTHER IRRIGATION
 OR PLUMBING CONTRACTOR. PLEASE NOTE THAT SUB-PERMIT
 APPLICATIONS MUST BE SUBMITTED AND ARE AT NO FEE IF
 SUBMITTED WITH THE MAIN PERMIT APPLICATION- SECTION
 105.1 WPB. AN ADDITIONAL FEE IS CHARGED FOR SUB-PERMITS
 SUBMITTED AFTER MASTER PERMIT ISSUANCE.
 RESPONSE; TO BE PROVIDED BY GC;
 PROVISO: IRR-1 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 ALL COMPONENTS OF THE HYDROPONIC IRRIGATION SYSTEM
 INCLUDING THE REVERSE OSMOSIS TREATMENT SYSTEM, BOOSTER
 PUMP, WATER STORAGE TANKS, PIPING AND TUBING, AND THE
 ADDITIONAL COMPONENTS LISTED ON THE PLAN SHEET AS
 DEFERRED SUBMITTALS TO PROVIDED AT A LATER DATE WITH
 THE ARCHITECT?S APPROVAL STAMP- SEE SECTIONS 107.1,
 107.3, AND 107.3.4.1 WPB AMENDMENTS TO THE FBC-17.
 MISSING DETAILS CAN BE PROVIDED ON THE PLANS, IN A
 SCHEMATIC DRAWING, OR BY DEFERRED SHOP DRAWINGS- FBC-17
 P:
 A) WATER TANK ANCHORAGE- SECTION 606.5.2.
 B) SHUT OFF VALVE LOCATIONS FOR TANKS AND EQUIPMENT-
 606.2 & 606.4.
 C) TANK OVERFLOW SYSTEM- 606.5.4.
 D) LOW PRESSURE CUTOFF FOR BOOSTER PUMP- 606.5.5
 E) POTABLE WATER INLET CONTROL AND LOCATION- 606.5.6.
 F) TANK DRAIN PIPES- 606.5.7.
 PROCEED AT YOUR OWN RISK
 REFER TO SEE RED LINED PLAN ?015 IRR-1 IRRIGATION
 PLAN-IRRIGATION ISOMETRIC-DETAILS?
  
  
 ADDITIONAL COMMENTS
 1.RE: P-2 SANITARY ISOMETRIC; THE UNDERGROUND COMMON
 VENTS NOTED ON THE DRAWING ARE PROHIBITED. SEE THE
 FOLLOWING. REFER TO SEE RED LINED PLAN ?014 P-2
 PLUMBING ISOMETRIC DETAILS? REGARDING FLOOR DRAIN AND
 BATHROOM VENTING
 A.FBC PL 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 B.FBC PL 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
 EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS.
 C.WET VENT FROM LAVATORY SHALL CONNECT TO THE FIXTURE
 DRAIN OF THE WATER CLOSET TO COMPLY WITH FBC PL 912.1
 HORIZONTAL WET VENTING. PLEASE NOTE THAT ACCORDING TO
 FBC PL CHAPTER 2 DEFINITIONS, A FLOOR DRAIN IN THE
 BATHROOM IS INCLUDED AS AN ALLOWABLE FIXTURE FOR A
 BATHROOM GROUP AND AS SUCH MAY BE CONNECTED TO THE WET
 VENT DOWNSTREAM OF THE WATER CLOSET AND WET VENT
 INTERSECTION WITHOUT RE-VENTING THE FLOOR DRAIN.
 D. THE THREE (3) FLOOR DRAINS DOWNSTREAM OF THE
 BATHROOMS, SINKS AND DRINKING FOUNTAIN SHALL BE VENTED
 BY ONE OF THE METHODS NOTED IN FBC PL CHAPTER 9.
 PLEASE SEE RED LINED PLAN ?014 P-2 PLUMBING ISOMETRIC
 DETAILS? REGARDING FLOOR DRAIN AND BATHROOM VENTING
 PLEASE SEE RED LINED PLAN ?013 P-1 PLUMBING FLOOR
 PLAN-ENLAGED PLAN-TRENCH INFILLS? REGARDING SLAB
 CUTTING/TRENCHING FOR FLOOR DRAINS
  
 2.PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING PLANS,
 THE LOCATION(S) AND MODEL OF THE BRADLEY S-19-200B
 FAUCET MOUNTED EYEWASH PROVIDED IN SUPPORTING
 DOCUMENTS. RESPONSE NOTED TWO LOCATIONS BUT IS NOT
 NOTED ON THE PLANS.
 PLEASE SEE RED LINED PLAN ?014 P-2 PLUMBING ISOMETRIC
 DETAILS?
  
 3. PROVIDE SPEC FOR IRRIGATION BACKFLOW PREVENTER WITH
 MANUFACTURER, AND MODEL. INDICATE TYPE (IE. REDUCED
 PRESSURE/RPZ). NOTE THE BACKFLOW PREVENTER IS DEDICATED
 TO THE IRRIGATION SYSTEM.
  
 4.PER WPB FBC107.2.1, SHOW ON THE PLANS THE LOCATION,
 SIZE AND TYPE OF THE BACKFLOW PREVENTER INSTALLED
 DOWNSTREAM OF THE CITY METER.
 PLEASE SEE RED LINED PLAN ?013 P-1 PLUMBING FLOOR
 PLAN-ENLAGED PLAN-TRENCH INFILLS? REGARDING BACKFLOW
 PREVENTER AT THE CITY METER
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS.
  