2021-03-12 11:08:32 | CODES IN EFFECT |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| 1) SHEET E-2 (KEYNOTE 7) AND SHEET E-5 (RISER DIAGRAM) |
| |
| FEEDER FROM MAIN 800 AMPS DISCONNECT TO PANEL LA IS NOW |
| SPECIFIED AS FOUR SETS OF 4#350 KCM (AL), 1#1/0 (CU). |
| THE FOUR SETS OF 4#350 KCM (AL) HAVE AN AMPACITY OF |
| 4X250 AMPS = 1000 AMPS. THE INCREASE IS PROBABLY TO |
| COMPENSATE FOR VOLTAGE DROP SINCE THE DISTANCE FROM |
| MAIN DISCONNECT TO PANEL LA IS VERY LONG. EQUIPMENT |
| GROUNDING CONDUCTORS WILL ALSO HAVE TO BE INCREASED |
| PROPORTIONALLY BY A FACTOR OF (350/250) = 1.4 TO COMPLY |
| WITH NEC 250.122 (B). THE EQUIPMENT GROUNDING CONDUCTOR |
| NEEDS TO BE A MINIMUM OF 3/0 CU NOW. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| |
| HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| MS |
| |
| ENRIQUE QUINONEZ P.E. |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |