2021-02-23 10:15:172ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20111108
 2/23/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IRR-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COMPONENTS OF THE HYDROPONIC IRRIGATION SYSTEM
 INCLUDING THE REVERSE OSMOSIS TREATMENT SYSTEM, BOOSTER
 PUMP, WATER STORAGE TANKS, PIPING AND TUBING, AND THE
 ADDITIONAL COMPONENTS LISTED ON THE PLAN SHEET. PLEASE
 NOTE THE SPECS MAY BE DEFERRED SUBMITTALS TO PROVIDED
 AT A LATER DATE WITH THE ARCHITECT?S APPROVAL STAMP-
 SEE SECTIONS 107.1, 107.3, AND 107.3.4.1 WPB AMENDMENTS
 TO THE FBC-17.
  
 2) PLEASE PROVIDE AN ITEMIZED BREAKDOWN OF COSTS
 ASSOCIATED WITH THE CHANGES IN THE PLANS AND PROJECTS
 INCLUDING THE IRRIGATION SYSTEM, ADDITIONAL TOILET
 ROOM, WATER HEATERS ETC.- SECTION 109.3 WPB.
  
 3) CLARIFY IF THE IRRIGATION SYSTEM WILL BE INSTALLED
 BY THE PLUMBING SUB-CONTRACTOR OR BY ANOTHER IRRIGATION
 OR PLUMBING CONTRACTOR. PLEASE NOTE THAT SUB-PERMIT
 APPLICATIONS MUST BE SUBMITTED AND ARE AT NO FEE IF
 SUBMITTED WITH THE MAIN PERMIT APPLICATION- SECTION
 105.1 WPB. AN ADDITIONAL FEE IS CHARGED FOR SUB-PERMITS
 SUBMITTED AFTER MASTER PERMIT ISSUANCE.
  
 4) P-2 & IRR-1: PROVIDE SUPPORT AND HANGING DETAILS FOR
 THE BACKFLOW PREVENTER AND IRRIGATION TUBING ARRAY
 SYSTEM- SECTION 305.2 AND 308.1 FBC P. PLEASE SHOW THE
 BACKFLOW ON SHEET P-2 AND PROVIDE A NOTE TO INDICATE A
 SEPARATE PERMIT IS REQUIRED FOR INSTALLATION- SECTION
 105.1 & 107.2.1 WPB.
  
 5) IRR-1 MISSING DETAILS CAN BE PROVIDED ON THE PLANS,
 IN A SCHEMATIC DRAWING, OR BE DEFERRED SHOP DRAWINGS-
 FBC-17 P:
  
 A) WATER TANK ANCHORAGE- SECTION 606.5.2.
 B) SHUT OFF VALVE LOCATIONS FOR TANKS AND EQUIPMENT-
 606.2 & 606.4.
 C) TANK OVERFLOW SYSTEM- 606.5.4.
 D) LOW PRESSURE CUTOFF FOR BOOSTER PUMP- 606.5.5
 E) POTABLE WATER INLET CONTROL AND LOCATION- 606.5.6.
 F) TANK DRAIN PIPES- 606.5.7.
  
 6) P-1 & P2: SHOW THE LOCATION OF THE EYEWASH STATION
 AND PROVIDE PLUMBING PIPING DETAILS IN ACCORDANCE WITH
 THE SUBMITTED MANUFACTURER?S SPECIFICATIONS- SECTION
 411.1 FBC P.
  
 7) P-2 POINT OF USE WH: A DEDICATED SHUTOFF VALVE IS
 REQUIRED FOR THE WATER SUPPLY PIPE TO THE WATER HEATER-
 SECTIONS 503.1 & 606.1. PLEASE NOTE SPECS FOR THE WATER
 HEATERS SHALL BE SUBMITTED OR BE DEFERRED. THE SPECS
 SHALL INDICATE ASSE 1070 CONFORMANCE OR A MIXING VALVE
 CONFORMING TO ASSE 1070 SHALL BE PROVIDED- SECTION
 607.1.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  