Plan Review Notes For Permit 20111108 |
Permit Number |
20111108 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-03-19 11:17:56 | FIRE PROVISO: | | | | THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED | | PER NFPA 101, CH 9 | | | | 9.7.2 SUPERVISION. | | 9.7.2.1* SUPERVISORY SIGNALS. | | 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS | | ARE REQUIRED BY | | ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS | | SHALL BE INSTALLED | | AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72, | | NATIONAL FIRE | | ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY | | SIGNAL SHALL BE | | PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE | | SATISFACTORY | | OPERATION OF THE SPRINKLER SYSTEM. | | 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE | | DISPLAYED EITHER AT | | A LOCATION WITHIN THE PROTECTED BUILDING THAT IS | | CONSTANTLY ATTENDED BY | | QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED | | RECEIVING | | FACILITY. | | | | PLEASE ENSURE COMPLIANCE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|