Plan Review Notes
Plan Review Notes For Permit 20111108
Permit Number 20111108
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-03-19 11:17:56FIRE PROVISO:
  
 THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED
 PER NFPA 101, CH 9
  
 9.7.2 SUPERVISION.
 9.7.2.1* SUPERVISORY SIGNALS.
 9.7.2.1.1 WHERE SUPERVISED AUTOMATIC SPRINKLER SYSTEMS
 ARE REQUIRED BY
 ANOTHER SECTION OF THIS CODE, SUPERVISORY ATTACHMENTS
 SHALL BE INSTALLED
 AND MONITORED FOR INTEGRITY IN ACCORDANCE WITH NFPA 72,
 NATIONAL FIRE
 ALARM AND SIGNALING CODE, AND A DISTINCTIVE SUPERVISORY
 SIGNAL SHALL BE
 PROVIDED TO INDICATE A CONDITION THAT WOULD IMPAIR THE
 SATISFACTORY
 OPERATION OF THE SPRINKLER SYSTEM.
 9.7.2.1.2 SUPERVISORY SIGNALS SHALL SOUND AND SHALL BE
 DISPLAYED EITHER AT
 A LOCATION WITHIN THE PROTECTED BUILDING THAT IS
 CONSTANTLY ATTENDED BY
 QUALIFIED PERSONNEL OR AT AN APPROVED, REMOTELY LOCATED
 RECEIVING
 FACILITY.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]