2020-12-23 17:07:551ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20111108
 12/23/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET S-4: TABLE 403.3 FBC P DOES NOT PROVIDE
 PLUMBING FIXTURE CALCULATIONS FOR UTILITY OCCUPANCIES.
 PLEASE REFER TO TABLE 1004.1.2 FBC B AND PROVIDE
 OCCUPANT LOAD CALCULATIONS AND THE CORRECT OCCUPANCY
 CLASSIFICATION ON THE PLANS. BASED ON THE BUILDING PLAN
 REVIEWER COMMENT #2B, AND THE FLORIDA FIRE PREVENTION
 ANALYSIS ON S-1, AN F OCCUPANCY IS ASSUMED FOR REVIEW
 PURPOSES. IN ACCORDANCE WITH TABLE 403.3 AND THE
 20-PERSON OCCUPANT LOAD SEPARATE WATER CLOSETS AND
 LAVATORIES ARE REQUIRED FOR MALE AND FEMALE USE. THERE
 ARE NO EXCEPTIONS UNDER SECTION 403.2 SEPARATE
 FACILITIES. IT APPEARS THE PLANS WILL HAVE TO REVISED
 TO PROVIDE SEPARATE TOILET ROOMS FOR MALE AND FEMALE
 USE. PLEASE NOTE THAT A DRINKING FOUNTAIN IS ALSO
 REQUIRED- SEE COMMENT #9 BELOW.
  
 2) P1 & P2: IT APPEARS THAT A MINIMUM OF ONE CLEANOUT
 WILL BE REQUIRED FOR THE 3-INCH SANITARY LINE BASED ON
 SECTION 708.1.1 FBC P.
  
 3) P2: PROVIDE A FULL OPEN SHUTOFF VALVE AT THE
 DISCHARGE SIDE OF THE NEW WATER METER- SECTION 606.1
 (3) FBC P.
  
 4) P2: INDICATE HOW TEMPERED WATER WILL PROVIDED TO THE
 LAVATORY- SECTIONS 416.5 & 607.1.2 FBC P. CLARIFY IF
 THE EEMAX POINT OF USE WATER HEATER IS ASSE 1070
 LISTED.
  
 5) P2: SHOW TRAP PRIMERS AT THE FLOOR DRAIN LOCATIONS-
 SECTION 1002.4.1 FBC P.
  
 6) P2: PLEASE NOTE THAT A FL. LICENSED PLUMBING
 CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 7) CLARIFY IF AN IRRIGATION SYSTEM WILL BE PROVIDED FOR
 THE HEMP GREENHOUSE. PLEASE PROVIDE PLAN DETAILS AND
 SHOW THE POINT OF CONNECTION TO THE POTABLE WATER
 SERVICE IF APPLICABLE- SECTION 107.2.1 WPB.
  
 8) S-4: PLEASE REMOVE THE + AND - SYMBOLS SHOWN AT THE
 ADA CLEARANCE DETAILS AND PROVIDE EXACT MEASUREMENTS-
 FBC-17 ACCESSIBILITY.
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
  
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
  
 C) TURNING SPACE DIAMETER- SECTION 304.3.
  
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
  
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
  
 F) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3.
  
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
  
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4.
  
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
  
 J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
  
 L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 9) S-4, P-1, P-2: BASED ON TABLE 403.3 FBC P A DRINKING
 FOUNTAIN IS REQUIRED FOR F OCCUPANCIES. REFER TO
 SECTION 211.2 FBC ACC- MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7. PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF
 THE FOUNTAINS AND PLUMBING PIPING DETAILS. REFER TO
 SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING
 FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS
 SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND
 SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO
 THE CIRCULATION PATH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  