2020-12-23 17:07:55 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20111108 |
| 12/23/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET S-4: TABLE 403.3 FBC P DOES NOT PROVIDE |
| PLUMBING FIXTURE CALCULATIONS FOR UTILITY OCCUPANCIES. |
| PLEASE REFER TO TABLE 1004.1.2 FBC B AND PROVIDE |
| OCCUPANT LOAD CALCULATIONS AND THE CORRECT OCCUPANCY |
| CLASSIFICATION ON THE PLANS. BASED ON THE BUILDING PLAN |
| REVIEWER COMMENT #2B, AND THE FLORIDA FIRE PREVENTION |
| ANALYSIS ON S-1, AN F OCCUPANCY IS ASSUMED FOR REVIEW |
| PURPOSES. IN ACCORDANCE WITH TABLE 403.3 AND THE |
| 20-PERSON OCCUPANT LOAD SEPARATE WATER CLOSETS AND |
| LAVATORIES ARE REQUIRED FOR MALE AND FEMALE USE. THERE |
| ARE NO EXCEPTIONS UNDER SECTION 403.2 SEPARATE |
| FACILITIES. IT APPEARS THE PLANS WILL HAVE TO REVISED |
| TO PROVIDE SEPARATE TOILET ROOMS FOR MALE AND FEMALE |
| USE. PLEASE NOTE THAT A DRINKING FOUNTAIN IS ALSO |
| REQUIRED- SEE COMMENT #9 BELOW. |
| |
| 2) P1 & P2: IT APPEARS THAT A MINIMUM OF ONE CLEANOUT |
| WILL BE REQUIRED FOR THE 3-INCH SANITARY LINE BASED ON |
| SECTION 708.1.1 FBC P. |
| |
| 3) P2: PROVIDE A FULL OPEN SHUTOFF VALVE AT THE |
| DISCHARGE SIDE OF THE NEW WATER METER- SECTION 606.1 |
| (3) FBC P. |
| |
| 4) P2: INDICATE HOW TEMPERED WATER WILL PROVIDED TO THE |
| LAVATORY- SECTIONS 416.5 & 607.1.2 FBC P. CLARIFY IF |
| THE EEMAX POINT OF USE WATER HEATER IS ASSE 1070 |
| LISTED. |
| |
| 5) P2: SHOW TRAP PRIMERS AT THE FLOOR DRAIN LOCATIONS- |
| SECTION 1002.4.1 FBC P. |
| |
| 6) P2: PLEASE NOTE THAT A FL. LICENSED PLUMBING |
| CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| FURTHER INFORMATION. |
| |
| 7) CLARIFY IF AN IRRIGATION SYSTEM WILL BE PROVIDED FOR |
| THE HEMP GREENHOUSE. PLEASE PROVIDE PLAN DETAILS AND |
| SHOW THE POINT OF CONNECTION TO THE POTABLE WATER |
| SERVICE IF APPLICABLE- SECTION 107.2.1 WPB. |
| |
| 8) S-4: PLEASE REMOVE THE + AND - SYMBOLS SHOWN AT THE |
| ADA CLEARANCE DETAILS AND PROVIDE EXACT MEASUREMENTS- |
| FBC-17 ACCESSIBILITY. |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE |
| WATER CLOSET- SECTION 604.3. |
| |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. |
| |
| C) TURNING SPACE DIAMETER- SECTION 304.3. |
| |
| D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL- |
| SECTION 604.2. |
| |
| E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| |
| F) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE |
| FINISHED FLOOR- SECTION 606.3. |
| |
| G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 306. |
| |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS- SECTION 604.5 & 609.4. |
| |
| I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION |
| 604.6. |
| |
| J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE |
| TOILET PAPER DISPENSER- SECTION 604.7. |
| |
| L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE |
| BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3. |
| |
| 9) S-4, P-1, P-2: BASED ON TABLE 403.3 FBC P A DRINKING |
| FOUNTAIN IS REQUIRED FOR F OCCUPANCIES. REFER TO |
| SECTION 211.2 FBC ACC- MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF |
| THE FOUNTAINS AND PLUMBING PIPING DETAILS. REFER TO |
| SECTIONS 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING |
| FOUNTAIN INSTALLATION DETAILS AND ELEVATION VIEWS |
| SHOWING KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, AND |
| SPOUT LOCATIONS. INDICATE HOW THE FOUNTAINS WILL BE IN |
| COMPLIANCE WITH SECTION 307.2- PROTRUDING OBJECTS INTO |
| THE CIRCULATION PATH. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |