2020-12-01 14:40:05 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 20111108 |
| ADD: 537 14TH ST. VERSES 514 14TH ST. |
| CONT: SR CONSTRUCTION SERVICES LLC |
| TEL: 561-301-9092 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 01/2020 |
| ACTION: DENIED |
| |
| 1) ADDRESS. PLEASE COORDINATE THE ADDRESS ON THE PERMIT |
| APPLICATION AND THE PLANS. THE PERMIT APPLICATION |
| STATES THE LOCATION OF THIS PROJECT IS 537 14TH ST. |
| WHEREAS THE PLANS HAVE ON THE COVERSHEET AND IN THE |
| TITLEBLOCK 514 14TH ST. |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED. |
| 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| ADDRESS IDENTIFICATION. |
| |
| 2) THE SHEET SP1 UNDER THE BUILDING CODE SUMMARY: |
| 2A) LIST THE BUILDING AS A CHANGE OF OCCUPANCY BUT LIST |
| THE ALTERATION AS A LEVEL 2. WHEN A BUILDING OR PORTION |
| OF THE BUILDING IS UNDERGOING A CHANGE OF OCCUPANCY |
| THEN YOU USE THE EXISTING BUILDING CODE CHAPTER 10 |
| CHANGE OF OCCUPANCY. SEE SECTION 1001.2.2 IF THE WHO |
| BUILDING IS UNDERGOING A CHANGE OF OCCUPANCY AND |
| SECTION 1001.2.2.1 IF ONLY A PORTION OF THE BUILDING IS |
| UNDERGOING A CHANGE OF OCCUPANCY. |
| |
| 2B) THE OCCUPANCY CLASSIFICATION IS INDICATED BEING A U |
| UTILITY OCCUPANCY. I BELIEVE THAT A F1 OCCUPANCY IS A |
| CLOSER FIT THAN A UTILITY OCCUPANCY. THE KEY THING IN |
| THE UTILITY OCCUPANCY IS FOUND IN THE 2017 FBC-B |
| SECTION 312.1 WHERE THE CODE STATES BUILDINGS AND |
| STRUCTURES OF AN ACCESSORY CHARACTER. YOU DO NOT HAVE |
| WHERE THIS IS ACCESSORY TO ANOTHER OCCUPANCY. THE |
| ACTUAL USAGE OF THE BUILDING IT WOULD APPEAR TO GROW |
| HEMP AND POSSIBLY PROCESS THE HEMP INTO VARIOUS |
| PRODUCTS. THE LAST KNOWN USE (BUSINESS LICENSE) WAS DNC |
| SERVICES BAGGED CONCRETE & MASONRY PRODUCTS OCCUPANCY |
| TYPE S-2 LOW-HAZARD. |
| |
| 2C) PLEASE UPDATE PLANS FOR BUILDING AREA & HEIGHT |
| CALCULATION FOR THE F1 OCCUPANCY PER 2017 FBC-B TABLE |
| 504.4 & TABLE 506.2. |
| |
| 2D) PLEASE ALSO UPDATE THE MAXIMUM EXIT ACCESS TRAVEL |
| DISTANCE FOR THE F1 OCCUPANCY 2017 FBC-B TABLE 1017.2. |
| |
| 2E) THERE IS NO HEADING FOR THE MAXIMUM COMMON PATH OF |
| TRAVEL, PLEASE UPDATE THE PLANS FOR (F) FACTORY |
| OCCUPANCY TABLE 1006.2.1. |
| |
| 2F) THE PLANS DO NOT PROVIDE AN OCCUPANT LOAD COUNT PER |
| TABLE 1004.1.2 OF THE 2017 FBC-B. |
| |
| 2G) THE SUBMITTED BUILDING CODE SUMMARY DOES NOT |
| PROVIDE A PLUMBING FIXTURE COUNT AS REQUIRED UNDER |
| TABLE 2902.10 OF THE 2017 FBC-B. |
| |
| 3) SHEET S-4 THE LIFE SAFETY SHEET ADA CLEARANCES AND |
| MOUNTING HEIGHTS ALL SHOW A +/- IN FRONT OF ALL |
| FIXTURES. PLEASE NOTE THAT WITHIN THE FBC-ACCESSIBILITY |
| CODE BOOK ALL MEASUREMENTS GIVEN ARE ABSOLUTES WITH THE |
| EXCEPTION OF THE WATER CLOSET FROM THE SIDE WALL WHICH |
| IS 16 -18 INCHES CENTER LINE AND THE GRAB BARS FOR THE |
| WATER CLOSET WHICH ARE 33-36 INCHES TOP OF THE GRASPING |
| SURFACE. 2017 FBC-ACCESSIBILITY CODE 201 DIMENSIONS. |
| |
| 4) SHEET S-4 THE LIFE SAFETY SHEET SHOWS THE PLUMBING |
| FIXTURE SCHEDULE BUT THERE IS NO HIGH-LOW DRINKING |
| FOUNTAIN INDICATED, NEITHER IS THERE ON THE LIFE SAFETY |
| FLOOR PLAN. |
| 4A) 2017 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| 4B) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2. |
| OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT |
| MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT PROTRUDE |
| MORE THAN 4 INCHES HORIZONTALLY INTO THE CIRCULATION |
| PATH. |
| |
| 4C) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| PROVIDED. |
| |
| 4D) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS. |
| CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR. |
| |
| 5) SHEET S-4 THE LIFE SAFETY SHEET SHOWS THE PRODUCTION |
| AREA WITH THE 300 SQ. FEET AS AN OCCUPANT LOAD FACTOR. |
| PLEASE REVIEW THE 300-OCCUPANT LOAD FACTOR IS TO BE |
| TAKEN WHEN STORAGE AND OR SHIPPING IS TIED TO A |
| MERCANTILE OCCUPANCY. THE WAREHOUSE AND SHIPPING |
| PORTION OF THE BUILDING DOES NOT PROVIDE INFORMATION AS |
| TO WHAT IS STORED THERE, WHAT QUANTITIES, IN RACK |
| STORAGE, IN CARDBOARD BOXES, SHIPPING PALLETS. |
| ADDITIONAL INFORMATION IS REQUIRED. 107.1.2.1. |
| |
| 6) SHEET S-4. THE PRODUCTION AREA IT WOULD BE ASSUMED |
| IS FOR HEMP. THE PLANS ARE SILENT S TO WHAT TYPE OF |
| CHEMICALS, FERTILIZERS WILL BE STORED ON SITE AND THE |
| QUANTITIES. PLEASE PROVIDE THEIR MSDS SHEETS. TO |
| DETERMINE COMPLIANCE WITH THE 2017 FBC-B TABLE 307.1.1. |
| |
| 7) SHEET S-4. THERE IS A LOBBY LOCATED BETWEEN THE WORK |
| AREA AND THE CLEAN VESTIBULE. BOTH DOORS SWING INTO |
| EACH OTHER, THEY ARE NOT IN COMPLIANCE WITH THE 2017 |
| FBC-ACCESSIBILITY CODE SECTION 404.2.6 DOORS IN SERIES. |
| THE DISTANCE BETWEEN 2 HINGED DOORS OR PIVOTED DOORS IN |
| SERIES SHALL BE 48 INCHES MINIMUM PLUS THE WIDTH OF |
| DOORS SWINGING INTO THE SPACE. SEE FIGURE 404.2.6. |
| |
| 8) SHEET S-9 INDICATES 5-INCH-THICK ICYNENE CLOSED CELL |
| BLOWN INSULATION R-19 OF THE EXISTING ROOF STRUCTURE |
| AND WALLS. PLEASE PROVIDE THE ICC REPORT FOR THE |
| ICYNENE. PLEASE ALSO PROVIDE HOW THE REQUIREMENTS FOR |
| THERMAL BARRIER (2603.4) AND IGNITION BARRIER |
| (2603.4.1.6) ARE TO BE MET. |
| |
| 9) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THERE MAYBE ADDITIONAL COMMENTS IN THE NEXT REVIEW |
| SINCE THERE ARE UNKNOWNS AND THE RESPONCES FROM THIS |
| REVIEW MAY REQUIRE ADDITIONAL COMMENTS FOR CODE |
| VARIFICATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |