Plan Review Notes For Permit 20111096 |
Permit Number |
20111096 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-24 16:22:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PLEASE PROVIDE A DETAILED SITE PLAN WITH SEPARATION | | DIMENSIONS TO ALL BUILDING WALLS. | | | | | | 2) PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT THIS | | TENT WILL BE USED AS/FOR. | | | | | | 3) PLEASE PROVIDE INDICATIONS OF ALL EXIT DOORS FROM | | THE BUILDING IN THE AREA OF WHERE THE TENT IS PROPOSED. | | | | THE TENT CAN NOT OBSTRUCT ANY EXIT OR RESTRICT PEOPLE | | FROM EXITING AWAY FROM THE BUILDING. | | | | | | 4) PLEAE PROVIDE AND PROPOSED FLOOR PLAN, LIGHTING, | | EXIT LIGHTS, FIRE EXTINGUISHERS, | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|