Plan Review Notes For Permit 20111068 |
Permit Number |
20111068 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-02-25 10:44:33 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1A.) FBC B 107.2.1, PROVIDE THE STRUCTURAL MAKE UP OF | | THE EXISTING EXTERIOR WALLS. THE FIRE RATING APPEARS TO | | BE OK BUT THE STRUCTURAL MAKE UP IS NOT CLEAR. PROVIDE | | THE STRUCTURAL DETAILS INCLUDING THE CALCULATIONS FOR | | THE WALLS AND TOP OF WALLS/PARAPET BEAMS AS THESE BEAMS | | WILL BE RECEIVING THE NEW FRAMED WALLS. | | | | 3A.) FBC B 1027.6, PLEASE INDICATE THE HEIGHT OF THE | | NEW CMU WALL AT THE EXTERIOR STAIRWAY(#2). | | | | 4.) & 5.) FBC B 107.2.1, PROVIDE THW WINDLOAD | | CALCULATIONS FOR THE NEW FRAMED WALLS TO BE ATTACHED TO | | TOP OF PARAPET WALLS AT BOTH EAST AND WEST SIDES. | | | | 11B.) FBC B 1014.2, THE LEFT SIDE OF PLAN SHEET A 8.0 | | (GUARDS AND HANDRAILS) HAVE NOT BEEN CORRECTED. THE | | DRAWING INDICATES THE GUARD & HANDRAIL STOP ON TOP OF | | THE FIRST TREAD, NOT THE LANDING, THAT PUTS THE | | GUARD/HANDRAIL TOO HIGH. PLEASE SEE FBC B SECTION | | 1014.2. |
|