2021-12-03 12:15:15 | 11/03/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE THE STANDARD BEING USED FOR THE |
| SIZING OF THE GREASE INTERCEPTOR. THE INTERCEPTOR SHALL |
| BE SIZED IN ACCORDANCE WITH ONE OF THE STANDARDS LISTED |
| IN 2017 FBC SEC. P 1003.3.4 OR RULE 64E-6 OF THE |
| FLORIDA ADMINISTRATIVE CODE AND THE CITY OF WEST PALM |
| BEACH STANDARD DETAIL GS-7. |
| |
| 2. PLEASE PLACE A NOTE THAT A SEPARATE PERMIT FOR THE |
| GREASE INTERCEPTOR IS REQUIRED BY A LICENSED CONTRACTOR |
| FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 105.1. |
| |
| 3. WASTES THAT DO NOT REQUIRE TREATMENT OR SEPARATION |
| SHALL NOT BE DISCHARGED INTO ANY INTERCEPTOR OR |
| SEPARATOR PER THE 2020 FBC SEC. P 1003.2 APPROVAL. HAND |
| SINKS ARE NOT ALLOWED TO GO INTO INTERCEPTOR. |
| |
| AS DISCUSSED IN CONVERSATION WITH ENGINEERING TEAM THE |
| COMMENTS THAT NEED TO BE ADDRESSED ON INTERCEPTOR MAY |
| BE DONE AT SEPARATE PERMIT SUBMITTAL FOR INTERCEPTOR. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |