2021-11-04 15:02:07 | 2ND REVIEW FBC-2020 MECHANICAL |
| PERMIT-20111068 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 4.0M: THE VENTILATION SCHEDULE SHOWS DINING, |
| FOOD PREP AND KITCHEN- COOKING. I DO NOT SEE INTERIOR |
| DINING, PLEASE SHOW THIS ON THE DRAWING. FOOD PREP IS |
| PART OF THE KITCHEN AND SHOULD BE COUNTED IN THE |
| KITCHEN SQ. FOOTAGE. I ALSO SEE A BAR WHICH SHOULD BE |
| LISTED ON THE OUTDOOR AIR CALCULATIONS. THE SCULLERY IS |
| ALSO PART OF THE KITCHEN. THE AREA SHOWN FOR FOOD |
| VENDOR IS 10 FT. 6 INCHES X 60 FT 2 INCHES. THIS IS |
| DOUBLED AS THERE ARE 2 AREAS FOR FOOD VENDORS. THIS IS |
| NOT SHOWN IN THE VENTILATION SCHEDULE. THE VENTILATION |
| SCHEDULE SHOWS 480 SQ FT FOR FOOD PREP AND 480 SQ. FT |
| KITCHEN COOKING. PLEASE PROVIDE ACCURATE CALCULATIONS |
| FOR EACH USE OF SPACE IN THIS TENANT SPACE. FBC 107.2.1 |
| |
| 2) I DO NOT SEE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. PLEASE SUBMIT THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS. FBC EC C403.2.1 |
| |
| 3) PLEASE PROVIDE SPECIFICATIONS FOR THE BATH EXHAUST |
| FANS. FBC 107.2.1 |
| |
| 4) PLEASE SHOW THE CONDENSATE DRAINAGE PIPE AND THE |
| TERMINATION. |
| FBC M 307 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |