2021-11-19 12:53:56 | PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| PERMIT # 20111068 522 CLEMATIS STREET. |
| 2ND REVIEW DENIED: |
| |
| 1A.) PENDING NOTE FROM LAST REVIEW: THE FLOOR PLAN |
| SHOWS EXISTING EXTERIOR WALLS BEING TERRA COTTA TILE: |
| |
| 1.) FBC B 706.6.1, STEPPED BUILDINGS, THE NEIGHBORING |
| BUILDINGS (ON BOTH SIDES) HAVE GLAZING THAT NEEDS TO BE |
| PROTECTED WITH NOT LESS THAN ? HOUR FIRE RATING AND THE |
| FRAMED WALL MUST HAVE NOT LESS THAN A 1 HOUR FIRE |
| RATING. (SEE PLAN SHEET A-4.1). |
| |
| 2.) FBC B 1027.5, EXIT EXTERIOR STAIRWAYS SHALL HAVE A |
| MINIMUM FIRE SEPARATION DISTANCE OF 10?. (SEE PLAN |
| SHEET LS-1 STAIR #2). |
| |
| 3.) FBC B 1027.6, EXTERIOR STAIRWAYS SHALL BE PROTECTED |
| WITH NOT LESS THAN A 1 HOUR FIRE RATING. |
| |
| 4.) FBC B 107.2.1, PLAN SHEET A-4.1 & A-11.0 INDICATES |
| A FRAMED WALL TO BE CONSTRUCTED OVER EXISTING PARAPET |
| WALL AT WHAT APPEARS TO BE THE WEST SIDE OF BUILDING. |
| PROVIDE CONNECTION DETAILS TO STRUCTURE BELOW. |
| |
| 5.) FBC B 107.2.1, PLAN SHEET A-2.0, A-11.0, & S-2.0 |
| INDICATES A FRAMED WALL TO BE CONSTRUCTED ON TOP OF |
| EXISTING PARAPET WALL AT THE EAST SIDE OF BUILDING. |
| PROVIDE CONNECTION DETAILS TO STRUCTURE BELOW. PLAN |
| SHEET S-2.0 ALSO INDICATES THAT THIS WALL IS TO BE A |
| CMU WALL. PLEASE CLARIFY IF THIS WALL IS TO BE A CMU |
| WALL OR A FRAMED WALL AND ALSO PROVIDE THE CONNECTION |
| DETAILS TO STRUCTURE BELOW. |
| |
| 1B.) CHANGE OF OCCUPANCY INFORMATION: |
| SHEET LS-1 HAS BEEN UPDATED. (SUBJECT TO ADDITIONAL |
| REVIEW PENDING NEWLY SUBMITTED MATERIAL). |
| 1C.) FBC EB 1102.3, VERTICAL ADDITION REQUIREMENTS: |
| DUE TO CONFLICTS IN CONSTRUCTION TYPE INDICATED (TYPE |
| VB) WITH OCCUPANCY (A-2) AND |
| THE ADDED THIRD STORY. THE BUILDING TYPE NEEDS TO BE |
| CORRECTED (POSSIBLY TO A TYPE |
| IIIB OR VA) PRIOR TO REVIEW. IN CHANGING THE BUILDING |
| TYPE THERE MAY BE ADDITIONAL |
| CONSIDERATIONS INCLUDING ENCLOSURE/FIRE RATING OF |
| INTERIOR STAIRWAY AND FIRE |
| RATING OF BUILDING MATERIALS. |
| 2A.) FBC B TABLE 1004.1.2, INDICATE ON PLAN SHEET |
| LS-1.1 (NON-FIXED CHAIRS ONLY) AT FOOD VENDOR QUEING |
| AREAS (1ST FLOOR). |
| 2B.) FBC B TABLE 1004.1.2, INDICATE ON PLAN SHEET LS |
| 1.1 (NON-FIXED CHAIRS ONLY) AT FUTURE VENDOR QUEING |
| AREAS (2ND FLOOR). |
| 2C.) NOTE: FIRE SPRINKLER REQUIREMENT IS NOTED ON PLAN |
| SHEET LS-1. SEPARATE FIRE SPRINKLER PERMIT IS TO BE |
| PROVIDED (FIRE SPRINKLER PLANS MUST CLEARLY INDICATE |
| ALL AREAS COVERED INCLUDING INTERSITIAL SPACES ABOVE |
| CEILINGS). |
| 2D.) OK, TOTAL OCCUPANCY IS BELOW 500 OCCUPANTS. |
| NOTE: |
| THE OWNER MAY HIRE A THIRD PARTY ENGINEERING FIRM TO |
| CERTIFY THE WELDED & BOLTED CONNECTIONS OF THE |
| STRUCTURAL STEEL. |
| AWS D1.1 CLAUSE 5.2 & 6.7: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELD PROCEDURE SPECIFICATION; THE W.P.S. |
| SPECIFIES THE REQUIRED ESSENTIAL VARIABLES INCLUDING: |
| BASE MATERIALS, JOINTS, PROCESS, AND FILLER METALS TO |
| BE USED. |
| AWS D1.1 CLAUSE 6.16: AT TIME OF INSPECTION PLEASE |
| PROVIDE A WELDER PERFORMANCE QUALIFICATION RECORD; THE |
| W.P.Q.R. PROVIDES INFORMATION WHICH CAN BE USED TO |
| VERIFY THE WELDER?S QUALIFICATION AND CERTIFICATION AS |
| IT RELATES TO THE WELDING REQUIREMENTS OF THE PROJECT. |
| 3.) OK, TOTAL OCCUPANCY IS BELOW 500 OCCUPANTS. |
| THEREFORE, THIS STRUCTURE WILL NOT BE CLASSIFIED AS A |
| THRESHOLD STRUCTURE. |
| 4.) FBC B TABLE 705.8, NO OPENINGS ARE PERMITTED AT |
| EAST SIDE OF BUILDING. PLAN SHEETS D1.0 & LS-1 INDICATE |
| DOOR OPENINGS. |
| NOTE: A UNITY OF TITLE WILL BE REQUIRED TO CONSIDER |
| PROPERTIES AS ONE. |
| 5A.) FBC B TABLE 602, PROVIDE DETAILED INFORMATION ON |
| PLAN SHEET LS-1 SHOWING THAT THE EXTERIOR WALL |
| ASSEMBLIES MEET THE (1) HOUR FIRE RATING. |
| 5B.) FBC B 706.6.1, 706.7, & 706.8; PROVIDE DETAILED |
| INFORMATION AS TO THE MAKE UP OF THE WALL OF THE WEST |
| BUILDING, (GOOGLE EARTH SITE SHOWS WHAT APPEARS TO BE A |
| WINDOW AT THIS LOCATION), THAT IS LOCATED ADJACENT TO |
| AND ABOVE THE ROOF LEVEL OF THIS PROJECT. |
| THE WINDOW IN THE EAST BUILDING WALL ADJACENT TO AND |
| ABOVE THE ROOF LEVEL APPEARS TO COMPLY WITH FBC B |
| 706.6.1 WITH NEW CMU WALL SHOWN ON PLAN SHEET S-2.0 AND |
| FBC EB 1101.1 & 1101.2. |
| 6.) OK, THE APPLICANT RESPONDED THAT THE REAR FLOOR IS |
| WOOD FRAMED AND THE FRONT AREA IS CONCRETE ON STRIP |
| FOOTINGS. ON DEMOLITION PLAN SHEET D-1.0 RESPONSIBILITY |
| IS NOTED IN DEMOLITION NOTES. |
| 7A.) OK, LIVE LOADS FOR ASSEMBLY AREAS SHOWN ON PLAN |
| SHEET LS-1. STAIRS, HANDRAILS, & GUARDS SHOWN ON PLAN |
| SHEET A-8.0. |
| 7B.) FBC B 1604.5, THE RISK CATEGORY SHOWN ON PLAN |
| SHEET S-1.0 IS RISK CATEGORY II. THIS APPEARS TO BE |
| INCORRECT. THE RISK CATEGORY, WITH AN OCCUPANT LOAD |
| GREATER THAN 300, SHOULD BE RISK CATEGORY III. |
| 8A.) FBC B TABLE 1604.5 AND FBC EB 1103.2/FBC EB |
| 907.4.2, ON PLAN SHEET S-1, THE RISK CATEGORY HAS NOT |
| BEEN UPDATED FROM II TO III AND THE ALTERATION LEVEL |
| HAS NOT BEEN UPDATED FROM II TO III. |
| 8B.) OK, REFER TO ITEM #8A TO CHANGE RISK CATEGORY II |
| TO III ON PLAN SHEET S-1. |
| 8C. OK, NOT CONSIDERED A THRESHOLD BUILDING PER FBC B |
| DEFINITIONS, AS TOTAL OCCUPANT LOAD HAS BEEN CLARIFIED. |
| 9.) OK, THE PRODUCT APPROVAL LIST HAS BEEN ADDED TO |
| PLAN SHEET CS-1 (COVER SHEET) WITH A NOTE STATING THAT |
| THE DEFERRED SUBMITTALS WILL BE REVIEWED AND FORWARDED |
| TO THE BUILDING OFFICIAL PRIOR TO INSTALLATION. THE |
| DESIGNER OF RECORD HAS ACKNOWLEDGED THE REQUIREMENTS |
| FOR DEFERRED SUBMITTALS. |
| 10.) FBC B TABLE 1017.2 AND FBC B 1017.3.1, PLEASE SHOW |
| THE ACTUAL EXIT ACCESS TRAVEL DISTANCE AND HOW IT |
| COMPLIES WITH THE FBC REQUIREMENTS. |
| 11A.) FBC B1011.5.2, PLAN SHEET A-8.0, LOCATED IN |
| PROJECT DOX, HAS NOT BEEN REVISED. THE NOTE FOR THE |
| STAIR RISERS MUST BE REVISED TO INDICATE THE STAIR |
| RISER HEIGHT CAN NOT EXCEED 7?. |
| 11B.) FBC B 1014.2, PLAN SHEET A-8.0, LOCATED IN |
| PROJECT DOX, HAS NOT BEEN REVISED. THERE FORE THE |
| DETAILS FOR HANDRAILS/GUARDS HAVE NOT CHANGED. |
| 12A.) OK, IT APPEARS THAT THE ELECTRIC ROOM IS BELOW |
| THE STAIR AND THE WALLS DOOR SEPARATING STAIR FROM |
| ELECTRIC ROOM ARE TO BE FIRE RATED IN ACCORDANCE WITH |
| FBC B 1023.2. |
| 12B.) FBC B 1027.5, FBC B 107.2.1, PROVIDE THE FIRE |
| RATING DETAILED INFORMATION OF NEW AND/OR EXISTING CMU |
| WALL ON PLAN. |
| 12C.) OK, PLAN SHEET LS-1.1 HAS BEEN UPDATED. |
| 13.) OK, CONNECTION DETAILS SHOWN ON PLAN SHEET |
| MEP3-A4.1. ALL PRODUCT APPROVALS INCLUDING ROOF TOP |
| EQUIPMENT HAVE TO BE ENGINEER REVIEW STAMP APPROVED. |
| 14.) FBC B FIGURE 1609.3(2)/LOCAL AMENDMENTS TO FBC B |
| FIGURE 1609.3(2), RISK FACTOR III MEANS THE WIND DESIGN |
| HAS TO MEET THE REQUIREMENTS OF 180 MPH VULT. PLEASE |
| CHANGE THE DESIGN REQUIREMENT FROM 170 MPH TO 180 MPH |
| ON RTU MOUNTING DETAIL, PLAN SHEET MEP3-A4.1. |
| 15.) FBC A, ACCESSIBILITY CODE, THE LIFE SAFETY PLAN |
| SHEETS LS-1 & LS-1.1 NEED TO INDICATE THE REQUIREMENTS |
| FOR ACCESSIBILITY INCLUDING SEATING & BAR TOP |
| MODIFICATIONS. |
| 15A.) FBC A 226.1, AT LEAST 5% OF SEATING AND STANDING |
| SPACES AT DINING SURFACES SHALL COMPLY WITH FBC A 902. |
| THIS MUST BE SHOWN ON PLANS. |
| 15B.) FBC A 226.2, THE DINING SURFACES, AS NOTED ABOVE, |
| MUST BE DISPERCED THROUGHOUT THE SPACE OR FACILITY. |
| THIS MUST BE SHOWN ON PLANS. |
| 15C.) OK, FBC A 206.2.5 & 206. ACCESSIBLE ROUTES SHOWN |
| INCLUDING PLAN SHEET LS-1. |
| 15D.) OK, FBC A 902.1, 902.2, & 902.3, PLAN SHEETS |
| A-9.0 & A-11.0 SHOW COMPLIANCE. |
| 15E(1) FBC A 902.2, 305, 306, THE CLEAR FLOOR SPACE |
| INCLUDING THE KNEE & TOE SPACE MUST BE SHOWN ON PLAN |
| SHEETS INCLUDING MEASUREMENT REQUIREMENTS. |
| 15E(2) OK, FBC A 902.3, PLAN SHEETS A-9.0 & A-11.0 SHOW |
| COMPLIANCE. |
| 16.) OK, THE RESTROOM CONFIGURATION IS SHOWN ON PLAN |
| SHEET A-1.0. |
| 17.) OK, FBC B 1210.2.2, PLAN SHEET A-5 SHOWS CERAMIC |
| TILE TO BE USED AT BATHROOM AREAS. |
| NOTE: FRP IS ALSO ACCEPTABLE BUT PAINT IS NOT. |
| 18.) PLEASE SEE IMPACT FEE REVIEW STOP. |
| 19.) TRANSMITTAL LETTERS/RESPONSE SHEETS ARE VERY |
| HELPFUL. PLEASE CONTINUE WITH THIS FORMAT OF RESPONSE. |
| |
| |
| |
| |
| |
| |