Plan Review Notes
Plan Review Notes For Permit 20111068
Permit Number 20111068
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-20 16:40:0505/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET CS-1, THE CODE REFERENCE IS FOR 2017
 ACCESSIBILITY IS NOT MENTION; PLEASE ADD PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET GN-2, ACCESSIBILITY NOTES;
  
 A. # 16 REFERS TO 18 INCHES FROM THE WALL TO THE
 CENTERLINE OF W.C., PLEASE GIVE CODE REFERENCE TO THAT
 APPLICATION OR CORRECT PER THE 2017 FBC ACC 604.2
 LOCATION.
  
 B. # 17 REFERS TO 15 INCHES TO 16 1/2 INCHES FROM THE
 CENTER OF THE WATER CLOSET; PLEASE GIVE CODE REFERENCE
 TO THAT APPLICATION OR CORRECT PER THE 2017 FBC ACC
 604.5.1 SIDE WALL.
  
 C. # 20 AND 21 IT SAYS 29 INCHES UNDER THE COUNTER;
 PLEASE CORRECT TO 27 INCHES PER THE 2017 FBC SEC. 306.3
 KNEE CLEARANCE.
  
 3. ON SHEET A-9.0;
  
 A. TOILET ACCESSORIES LEGEND NOTE #1 AND 3, GRAB BARS,
 SAYS TO CENTER PLEASE CORRECT TO THE TOP PER THE 2017
 FBC ACC 609.4 POSITION OF GRAB BARS. PLEASE CORRECT
 ELEVATION A AS WELL.
  
 B. ON ELEVATION A UNDER TYPICAL HANDICAP STALL DETAILS,
 ELEVATION B, DETAIL MEN'S RESTROOM AND WOMAN'S RESTROOM
 DETAIL B, PLEASE SHOW THAT THE MIRROR TO REFLECTIVE
 PART OF THE MIRROR NEEDS TO BE 4 INCHES TO THE
 REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. 603.3.
  
 C. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS
 AND PLACE CLEARANCE REQUIREMENTS, PLEASE SHOW THAT THE
 WATER CLOSET SHALL BE 16 INCHES TO 18 INCHES PER THE
 2017 FBC ACC SEC. 604.2 LOCATION.
  
 D. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS,
 AND PLACE CLEARANCE REQUIREMENTS FOR THE REAR GRAB BAR
 NEED TO COMPLY PER THE 2017 FBC ACC SEC. 604.5.2 REAR
 WALL. 6" MAX IS NOT THE CODE.
  
 E. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS,
 AND PLACE CLEARANCE REQUIREMENTS FOR THE TOILET PAPER
 HOLDER SHALL BE 7" INCHES MINIMUM AND 9" INCHES MAXIMUM
 IN FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE
 OF DISPENSER PER THE 2017 FBC ACC SEC. 604.7.
  
 F. ON TOILET ACCESSORIES LEGEND, PLACE A NOT THAT DOOR
 HANDLE HARDWARE SHOULD BE NOTED ON BOTH SIDES OF THE
 DOOR PER THE 2017 FBC ACC SEC. 404.2.7. THE LOCATION
 OPEN SIDE OF THE WATER CLOSET FOR THE FLUSH CONTROL PER
 THE 2017 FBC SEC. 604.6 FLUSH CONTROLS.
  
 G. ON THE DETAIL RESTROOMS, PLEASE SHOW ALL CLEAR FLOOR
 SPACE AND DIMENSIONS FOR STALLS, HANDICAP LAV OUTSIDE
 THE STALL, AND URINAL PER THE 2017 FBC ACC SEC. 602.2.
  
 H. ON DETAIL MEN'S ROOM HANDICAP URINAL, PLEASE SHOW
 THE URINALS SHALL BE 17 INCHES WHICH SHALL BE A
 MAXIMUM, AND 13 1/2 INCHES PER THE 2017 FBC ACC. SEC.
 605.2.
  
 I. TOILET ACCESSORIES LEGEND NOTE # 7 THE TOILET SEATS
 NEED TO BE 17 INCHES TO 19 INCHES MAXIMUM MEASURED TO
 THE TOP OF THE SEAT PER THE 2017 FBC ACC SEC. 604.4
 SEATS, AND THAT SEAT NEEDS TO BE OPEN FRONT, 2017 FBC P
 420.3 WATER CLOSET SEATS.
  
 J. ON THE DETAIL RESTROOMS, PLEASE SHOW THE HEIGHT FOR
 ALL PARTITIONS BETWEEN THE URINAL PER THE 2017 FBC SEC.
 P 405.3.5.
  
 K. ON DETAIL FOR THE RESTROOMS PLAN, THE OPENING FOR
 THE URINAL AND TOILET IN THE MEN'S ROOM IS AT 2 FOOT 6
 INCHES, AND THIS MAY NOT WORK WHEN PARTITION. THE
 WOMAN'S RESTROOM HAS 2 FOOT 8 INCHES, SO PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET 3.0P, THE TEMPERING VALVE SHALL COMPLY WITH
 ASSE 1070 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER
 FOR PUBLIC HAND-WASHING FACILITIES.
  
 PLEASE PROVIDE THE STANDARD BEING USED FOR THE SIZING
 OF THE GREASE INTERCEPTOR. THE INTERCEPTOR SHALL BE
 SIZED IN ACCORDANCE WITH ONE OF THE STANDARDS LISTED IN
 2017 FBC SEC. P 1003.3.4 OR RULE 64E-6 OF THE FLORIDA
 ADMINISTRATIVE CODE AND THE CITY OF WEST PALM BEACH
 STANDARD DETAIL GS-7.
  
 PLEASE PLACE A NOTE THAT A SEPARATE PERMIT FOR THE
 GREASE INTERCEPTOR IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  
 PLEASE PROVIDE A LEGEND FOR ALL EQUIPMENT BEING USED ON
 ALL FLOORS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE PLACE A NOTE THAT THE SERVICE SINK (MOP SINK)
 SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE
 IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2
 AND 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS
 SHEET.
  
 ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2017 FBC SEC. 608.13.10.
  
 SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE VACUUM
 BREAKER THAT COMPLIES WITH ASSE 1022 PER THE 2017 FBC
 SEC. 608.16.1.
  
  
 5. ON SHEEP 3.3P;
  
 A. THE ISOMETRIC DRAWING SHOWS A TANK; PLEASE PROVIDED
 DETAIL FOR THE RECIRCULATING PUMP, CHECK VALVES,
 SHUT-OFF VALUES, THERMAL EXPANSION, AND DRAIN TO THE
 OUTSIDE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE RECALCULATING SYSTEM SHALL BE SIZED PER 2017 FBC
 CE TABLE C404.5.1 PIPING VOLUME AND MAXIMUM PIPING
 LENGTHS.
  
 C. HOT WATER LINE UNDER SLAB SHALL BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. CE 403.5.3.
  
 D. PLEASE NOTE THE SIZE OF INSULATION FOR THE HOT WATER
 RETICULATING SYSTEM PER THE 2017 FBC CE 404.4
 INSULATION OF PIPING.
  
 E. PLEASE SHOW ALL HAMMER ARRESTORS IN COMPLIANCE WITH
 THE 2017 FBC SEC. FBC P 604.9.
  
 F. IF SHUT VALUES ARE IN THE CEILING, HOW WILL THEY
 HAVE ACCESS, OR ARE THEY IN AN ACCESS PANEL? PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
2021-05-18 09:02:13ENTERED BY MISTAKE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved