Date |
Text |
2021-05-20 16:40:05 | 05/20/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET CS-1, THE CODE REFERENCE IS FOR 2017 |
| ACCESSIBILITY IS NOT MENTION; PLEASE ADD PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. ON SHEET GN-2, ACCESSIBILITY NOTES; |
| |
| A. # 16 REFERS TO 18 INCHES FROM THE WALL TO THE |
| CENTERLINE OF W.C., PLEASE GIVE CODE REFERENCE TO THAT |
| APPLICATION OR CORRECT PER THE 2017 FBC ACC 604.2 |
| LOCATION. |
| |
| B. # 17 REFERS TO 15 INCHES TO 16 1/2 INCHES FROM THE |
| CENTER OF THE WATER CLOSET; PLEASE GIVE CODE REFERENCE |
| TO THAT APPLICATION OR CORRECT PER THE 2017 FBC ACC |
| 604.5.1 SIDE WALL. |
| |
| C. # 20 AND 21 IT SAYS 29 INCHES UNDER THE COUNTER; |
| PLEASE CORRECT TO 27 INCHES PER THE 2017 FBC SEC. 306.3 |
| KNEE CLEARANCE. |
| |
| 3. ON SHEET A-9.0; |
| |
| A. TOILET ACCESSORIES LEGEND NOTE #1 AND 3, GRAB BARS, |
| SAYS TO CENTER PLEASE CORRECT TO THE TOP PER THE 2017 |
| FBC ACC 609.4 POSITION OF GRAB BARS. PLEASE CORRECT |
| ELEVATION A AS WELL. |
| |
| B. ON ELEVATION A UNDER TYPICAL HANDICAP STALL DETAILS, |
| ELEVATION B, DETAIL MEN'S RESTROOM AND WOMAN'S RESTROOM |
| DETAIL B, PLEASE SHOW THAT THE MIRROR TO REFLECTIVE |
| PART OF THE MIRROR NEEDS TO BE 4 INCHES TO THE |
| REFLECTIVE SIDE PER THE 2017 FBC ACC SEC. 603.3. |
| |
| C. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS |
| AND PLACE CLEARANCE REQUIREMENTS, PLEASE SHOW THAT THE |
| WATER CLOSET SHALL BE 16 INCHES TO 18 INCHES PER THE |
| 2017 FBC ACC SEC. 604.2 LOCATION. |
| |
| D. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS, |
| AND PLACE CLEARANCE REQUIREMENTS FOR THE REAR GRAB BAR |
| NEED TO COMPLY PER THE 2017 FBC ACC SEC. 604.5.2 REAR |
| WALL. 6" MAX IS NOT THE CODE. |
| |
| E. ON ELATION A UNDER TYPICAL HANDICAP STALL DETAILS, |
| AND PLACE CLEARANCE REQUIREMENTS FOR THE TOILET PAPER |
| HOLDER SHALL BE 7" INCHES MINIMUM AND 9" INCHES MAXIMUM |
| IN FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE |
| OF DISPENSER PER THE 2017 FBC ACC SEC. 604.7. |
| |
| F. ON TOILET ACCESSORIES LEGEND, PLACE A NOT THAT DOOR |
| HANDLE HARDWARE SHOULD BE NOTED ON BOTH SIDES OF THE |
| DOOR PER THE 2017 FBC ACC SEC. 404.2.7. THE LOCATION |
| OPEN SIDE OF THE WATER CLOSET FOR THE FLUSH CONTROL PER |
| THE 2017 FBC SEC. 604.6 FLUSH CONTROLS. |
| |
| G. ON THE DETAIL RESTROOMS, PLEASE SHOW ALL CLEAR FLOOR |
| SPACE AND DIMENSIONS FOR STALLS, HANDICAP LAV OUTSIDE |
| THE STALL, AND URINAL PER THE 2017 FBC ACC SEC. 602.2. |
| |
| H. ON DETAIL MEN'S ROOM HANDICAP URINAL, PLEASE SHOW |
| THE URINALS SHALL BE 17 INCHES WHICH SHALL BE A |
| MAXIMUM, AND 13 1/2 INCHES PER THE 2017 FBC ACC. SEC. |
| 605.2. |
| |
| I. TOILET ACCESSORIES LEGEND NOTE # 7 THE TOILET SEATS |
| NEED TO BE 17 INCHES TO 19 INCHES MAXIMUM MEASURED TO |
| THE TOP OF THE SEAT PER THE 2017 FBC ACC SEC. 604.4 |
| SEATS, AND THAT SEAT NEEDS TO BE OPEN FRONT, 2017 FBC P |
| 420.3 WATER CLOSET SEATS. |
| |
| J. ON THE DETAIL RESTROOMS, PLEASE SHOW THE HEIGHT FOR |
| ALL PARTITIONS BETWEEN THE URINAL PER THE 2017 FBC SEC. |
| P 405.3.5. |
| |
| K. ON DETAIL FOR THE RESTROOMS PLAN, THE OPENING FOR |
| THE URINAL AND TOILET IN THE MEN'S ROOM IS AT 2 FOOT 6 |
| INCHES, AND THIS MAY NOT WORK WHEN PARTITION. THE |
| WOMAN'S RESTROOM HAS 2 FOOT 8 INCHES, SO PLEASE CORRECT |
| PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. ON SHEET 3.0P, THE TEMPERING VALVE SHALL COMPLY WITH |
| ASSE 1070 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER |
| FOR PUBLIC HAND-WASHING FACILITIES. |
| |
| PLEASE PROVIDE THE STANDARD BEING USED FOR THE SIZING |
| OF THE GREASE INTERCEPTOR. THE INTERCEPTOR SHALL BE |
| SIZED IN ACCORDANCE WITH ONE OF THE STANDARDS LISTED IN |
| 2017 FBC SEC. P 1003.3.4 OR RULE 64E-6 OF THE FLORIDA |
| ADMINISTRATIVE CODE AND THE CITY OF WEST PALM BEACH |
| STANDARD DETAIL GS-7. |
| |
| PLEASE PLACE A NOTE THAT A SEPARATE PERMIT FOR THE |
| GREASE INTERCEPTOR IS REQUIRED BY A LICENSED CONTRACTOR |
| FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 105.1. |
| |
| PLEASE PROVIDE A LEGEND FOR ALL EQUIPMENT BEING USED ON |
| ALL FLOORS PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| PLEASE PLACE A NOTE THAT THE SERVICE SINK (MOP SINK) |
| SURROUNDING THE WALL SHALL BE A NON-ABSORBENT SURFACE |
| IN ACCORDANCE WITH THE 2017 FBC BUILDING SEC. 1210.2.2 |
| AND 2017 FBC SEC. P 310.3. PLEASE MAKE A NOTE ON THIS |
| SHEET. |
| |
| ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN |
| IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER |
| THE 2017 FBC SEC. 608.13.10. |
| |
| SODA MACHINES SHALL BE EQUIPPED WITH AN IN-LINE VACUUM |
| BREAKER THAT COMPLIES WITH ASSE 1022 PER THE 2017 FBC |
| SEC. 608.16.1. |
| |
| |
| 5. ON SHEEP 3.3P; |
| |
| A. THE ISOMETRIC DRAWING SHOWS A TANK; PLEASE PROVIDED |
| DETAIL FOR THE RECIRCULATING PUMP, CHECK VALVES, |
| SHUT-OFF VALUES, THERMAL EXPANSION, AND DRAIN TO THE |
| OUTSIDE PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| B. THE RECALCULATING SYSTEM SHALL BE SIZED PER 2017 FBC |
| CE TABLE C404.5.1 PIPING VOLUME AND MAXIMUM PIPING |
| LENGTHS. |
| |
| C. HOT WATER LINE UNDER SLAB SHALL BE INSULATED WITH A |
| MINIMUM R-3 PER THE 2017 FBC SEC. CE 403.5.3. |
| |
| D. PLEASE NOTE THE SIZE OF INSULATION FOR THE HOT WATER |
| RETICULATING SYSTEM PER THE 2017 FBC CE 404.4 |
| INSULATION OF PIPING. |
| |
| E. PLEASE SHOW ALL HAMMER ARRESTORS IN COMPLIANCE WITH |
| THE 2017 FBC SEC. FBC P 604.9. |
| |
| F. IF SHUT VALUES ARE IN THE CEILING, HOW WILL THEY |
| HAVE ACCESS, OR ARE THEY IN AN ACCESS PANEL? PLEASE |
| CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |
2021-05-18 09:02:13 | ENTERED BY MISTAKE. |