2021-05-13 10:42:05 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-20111068 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THIS |
| CHANGE OF OCCUPANCY A-2. PLEASE INCLUDE ALL SPACES OF |
| THIS PROJECT. FBC M 403.3.1.1 & TABLE 403.3.1.1 |
| |
| 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR THIS CHANGE OF USE. FBC EC C403.2.1 |
| |
| 3) PLEASE SHOW THAT THE RESTROOM EXHAUST CAP WILL MEET |
| FBC M 501.3 AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC, |
| CRAWL SPACE, OR BE DIRECTED ONTO WALKWAYS. |
| |
| 4) THE HOODS WILL NOT BE REVIEWED AT THIS TIME, PLEASE |
| REMOVE THE HOOD DRAWINGS FROM THIS SUBMITTAL AND |
| RESUBMIT UNDER A SEPARATE PERMIT. PLEASE PROVIDE A NOTE |
| ON THE PLANS THAT STATES THE KITCHEN HOODS AND ANY |
| REFRIGERATION WILL NEED TO BE SUBMITTED SEPARATELY AND |
| MUST HAVE SEPARATE PERMITS AND REVIEWS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |