Plan Review Notes
Plan Review Notes For Permit 20111068
Permit Number 20111068
Review Stop G
Sequence Number 1
Notes
Date Text
2021-05-21 11:47:5105/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 ON SHEET 3.3P;
  
 1. THE CODE REFERENCES IS 5 TH EDITION 2014 PLEASE
 CHANGE TO 2017 6 TH EDITION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 102.4 REFERENCED CODES AND STANDARDS.
  
 2. PLEASE PROVIDE A VALVE AT THE END OF THE RUN WITH
 CAP FOR FUTURE USE PER THE 2017 FBC FG SEC. 409.5.
  
 3. PLEASE SHOW THE VALVE AND REGULATORS. A LISTED
 SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC FG SEC. 409.4.
  
 4. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC OR
 SHOW SYMBOL ON LEGEN PER THE 2017 FBC FG SEC. 409.5.
  
 5. THE BEGINNING OF THE GAS SYSTEM HAS NO SIZE OR
 DIMENSION, PLEASE SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES FOR EACH PIPE SIZE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. PLEASE GIVE THE DISTANCE FROM THE POINT OF DELIVERY,
 GAS METER TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE 2017 FBC FG SEC. 402.4.1.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR TANKLESS GAS EQUIPMENT
 TO VERIFY COMPLIANCE WITH 2017 FBC FG SEC.305.1.
  
 8. A REGULATOR IS REQUIRED TO BRING THE SYSTEM DOWN TO
 10.5 WC. PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. 410.1.
  
 9. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1' OF
 EITHER SIDE PER THE FBC FG SEC 410.2.
  
 10. GAS UNITS REQUIRE CONDENSATE AND THEY NEED TO BE 1'
 AWAY FROM STRUCTURE AND TO A SAFE LOCATION ( NOT INTO
 SANITARY SYSTEM) PER THE 2017 FBC SEC R318.5.
  
 11. SHOWING THE LOCATION OF THE TANK-LESS WATER HEATER
 AND THE LOCATION WITH THE DISTANCE OF ANY OPERABLE
 DOORS OR WINDOWS IN RELATION TO THE WATER HEATER AND TO
 EACH UNIT. THE LOCATION OF THE WATER HEATER SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  