Plan Review Notes
Plan Review Notes For Permit 20111068
Permit Number 20111068
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-04-21 12:13:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) LS 1 - THERE ARE INDICATIONS OF OCCUPANCY LOAD
 CALCULATIONS; HOWEVER, THERE ARE NO INDCATIONS OF THE
 EXIT DOOR OPENING AND CORRIDOR WIDTH DIMENSIONS.
  
 PER NFPA 101 CH 7 MEANS OF EGRESS
  
 7.3 CAPACITY OF MEANS OF EGRESS
 7.3.1 OCCUPANT LOAD.
 7.3.1.1 SUFFICIENT CAPACITY.
 7.3.1.1.1 THE TOTAL CAPACITY OF THE MEANS OF EGRESS FOR
 ANY STORY, BALCONY,
 TIER, OR OTHER OCCUPIED SPACE SHALL BE SUFFICIENT FOR
 THE OCCUPANT
 LOAD THEREOF UNLESS ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
 (1) THE AUTHORITY HAVING JURISDICTION SHALL BE
 PERMITTED TO ESTABLISH
 THE OCCUPANT LOAD AS THE NUMBER OF PERSONS FOR WHICH
 EXISTING
 MEANS OF EGRESS IS ADEQUATE, PROVIDED THAT MEASURES ARE
 ESTABLISHED
 TO PREVENT OCCUPANCY BY A GREATER NUMBER OF PERSONS.
 (2) THE EGRESS CAPACITY SHALL HAVE BEEN PREVIOUSLY
 APPROVED AS BEING
 ADEQUATE.
 7.3.1.1.2 FOR OTHER THAN EXISTING MEANS OF EGRESS,
 WHERE MORE THAN ONE
 MEANS OF EGRESS IS REQUIRED, THE MEANS OF EGRESS SHALL
 BE OF SUCH WIDTH
 AND CAPACITY THAT THE LOSS OF ANY ONE MEANS OF EGRESS
 LEAVES AVAILABLE
 NOT LESS THAN 50 PERCENT OF THE REQUIRED CAPACITY.
  
 WHAT ARE THE OCCUPANT TOTALS FOR EACH OPENING THAT
 ACCOUNT FOR ALL THE PROPOSED OCCUPANTS?
  
 PLEASE PROVIDE DETAILS SHOWING COMPLIANCE.
  
  
  
 2) LS 1 - THE OCCUPANCY LOAD CALCULATIONS INDICATE
 15SF/PERSON; HOWEVER, THERE ARE NO INDICATIONS OF
 TABLES AND CHAIRS.
  
 THE 1ST FLOOR INDICATES VERY LIMITED SPACE THAT APPEARS
 TO WITHIN THE EXIT TRAVEL PATH WHERE TABKLES AND CHAIRS
 CAN NOT BE PLACED.
  
 I AM NOT SURE WHAT THE ACTUAL DIMENSIONS ARE FOR
 STANDING/WAITING LINES OR THOSE AREAS FOR TABLES AND
 CHAIRS.
  
 BASED ON WHAT HAS BEEN PROVIDED, I DO NOT SEE
 SUFFICIENT AREA FOR 231 OCCUPANTS FOR THE 1ST FLOOR NOR
 183 FOR THE 2ND FLOOR.
  
 PLEASE PROVIDE GREATER DETAIL, DIMENSIONS AND PROVIDE
 SEATING PLAN AND BAR PLAN.
  
  
  
  
 3) LS 1 - THERE IS AN INDICATION OF AN EXTERIOR YARD
 WITH AN OCCUPANCY LOAD OF 57 OCCUPANNTS.
  
 THERE IS LIMITED INFORMATION IN THIS AREA. THE ONE WALL
 SEEMS TO END.
  
 IS THAT AREA OPEN FOR FREE EGRESS OR DO ALL OCCUPANTS
 ENTERING THAT SPACE NEED TO EXIT THROUGH THE DOUBLE
 DOORS?
  
 IS IT CONCRETE FLOOR/GROUND/PAVEMENT?
  
 THAT AREA ALSO SERVES AND THE EXIT ACCESS FOR THE OTHER
 AREAS AND THE EXIT ACCESS MUST BE UNOSTRUCTED.
  
 PLEASE PROVIDE GREATER DETAIL WITH DIMENSIONS WITH ANY
 PROPOSED SEATING PLANS.
  
  
  
 4) A 5.0 - THE DOOR SCHEDULE INDICATES HARDWARE BY MFR.
  
 THIS IS AN ASSEMBLY OCCUPANCY THAT REQUIRES HARDWARE
 PER NFPA 101.
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED
 WITH A LATCH OR LOCK ONLY IF THE LATCH OR LOCK IS PANIC
 HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCKING
 SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6.
  
 PLEASE PROVIDE THE REQUIRED HARDWARE ON EACH EXIT
 DOOR/GATE, INCLUDING THE OUTSIDE DOUBLE EXIT DOORS, IN
 COMPLIANCE.
  
  
  
  
 5) MECHANICAL HOOD - ALL WORK FOR THE HOOD AND
 SUPPRESSION SYSTEMS SHALL BE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  