2021-04-20 12:24:12WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20111068 / 2017 FBC
 ADD: 522 CLEMATIS ST.
 CONT: TBD/ TO BE DETERMINED / CONTACT: JESSICA ROLLINGS
 TEL: ???
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. APRIL 19TH/ 2021
 ACTION: DENIED
  
 1A) THE PERMIT APPLICATION DESCRIPTION OF WORK
 DESCRIBES THE RENOVATION AND INTERIOR IMPROVEMENTS INTO
 A NEW FOOD MARKETPLACE. IT WOULD APPEAR THERE IS NO
 FOOD MARKET AS PER SAY A GROCERY STORE BUT MULTIPLE
 FOOD VENDORS ON THE 1ST FLOOR A A2 OCCUPANCY AN A2
 OCCUPANCY AND A NEW VERTICAL ADDITION CREATING A ROOF
 TOP 2ND STORY. PEASE NOTE YES YOU MAY CLAIM A LEVEL 3
 ALTERATION TO THE 1ST FLOOR. PLEASE REVIEW ALL OF THE
 STRUCTURAL REQUIREMENTS FOUND IN THE 2017 FBC-EXISTING
 BUILDING CODE IN THE STRUCTURAL SECTION 907.1- 907.4.2.
 THE FLOOR PLAN SHOWS THE EXISTING EXTERIOR WALLS BEING
 TERRA-COTTA TILE.
  
 1B) THERE IS ANOTHER ISSUE TO BE CONSIDERED, THE LAST
 KNOWN USE. THE LAST KNOWN USE (BUSINESS TAX/
 OCCUPATIONAL LICENSE) WAS FOR AUTHENTIC PROVENCE INC. A
 MERCANTILE USE WHERE THEY SOLD RETAIL GARDEN
 ACCESSORIES, GARDEN EQUIPMENT, RETAIL SUPPLIES AND
 NURSERY. UNDER THE REQUIREMENTS IN THE2017 EXISTING
 BUILDING CODE FOR A CHANGE OF OCCUPANCY FOR A BUILDING
 YOU MUST ALSO SHOW COMPLIANCE FOR SECTIONS 1002 THROUGH
 1012 OF THE EXISTING BUILDING CODE SHALL ALSO APPLY.
 UNDER THE PROJECT DETAILS YOU NEED TO ALSO ADD THE
 SECTION REQUIREMENT FOR CHANGE OF OCCUPANCY.
  
 1C) THE 3RD ISSUE IS THE VERTICAL ADDITION REQUIREMENTS
 FOUND IN THE 2017 FBC-BUILDING CHAPTER 11, 1102.1,
 1102.2 1102.3 1103.2 ADDITIONAL GRAVITY LOADS AND
 1105.1 ACCESSIBILITY REQUIREMENTS. SEE THE 2020
 FBC-ACCESSIBILITY CODE.
  
 2) THE COVERSHEET CS-1 VERSES THE LIFE-SAFETY SHEET:
  
 2A) THE 1ST FLOOR OCCUPANT LOAD ANALYSIS IS TAKEN @ 15
 SQ. FT./ OCCUPANT. DIRECTLY IN FRONT OF EACH OF THE
 VENDOR STANDS WHERE THERE IS STANDING ONLY THE OCCUPANT
 LOAD SHOULD BE TAKEN AT 5SQ. FT./ OCCUPANT, TAKING THE
 15 SQ. FT. IS FOR TABLE AND CHAIRS WHICH ARE NOT SHOWN
 ON THE 1ST FLOOR LIFE SAFETY PLAN.
  
 2B) THE 2ND FLOOR LIFE SAFETY PLAN HAS ALSO TAKEN THE
 15 SQ. FT. OCCUPANT LOAD FOR TABLES AND CHAIRS WHEREAS
 THE ONLY THING SHOWN ON THE 2ND FLOOR IS THE BAR NO
 CHAIRS WHERE THE 5 FEET PER OCCUPANT LOAD IS CORRECT.
 THE WORST-CASE SCENARIO HAS TO BE TAKEN SINCE THE 2ND
 FLOOR DOES NOT SHOW A SEATING FLOOR PLAN.
  
 2C) THE COVERSHEET STATES THIS BUILDING CONSTRUCTION
 TYPE TO BE TYPE V-B SPRINKLERED. PLEASE NOTE TO HAVE
 CONSTRUCTION TYPE V-B BUILDING IT IS REQUIRED TO BE A
 SPRINKLERED BUILDING AS REQUIRED BY TABLE 504.4 OF THE
 2017 FBC-B. THIS REVIEW THERE WERE NO PRE-LIMINARY FIRE
 SPRINKLER DRAWINGS FROM THE ARCHITECT. PLEASE PROVIDE
 WHAT AREAS OF THE BUILDING ARE GOING TO BE FIRE
 SPRINKLERED. 1ST FLOOR BELOW CEILING, ABOVE CEILING,
 INTERSTITIAL SPACE BETWEEN ROOF AND 2ND FLOOR FRAMING
 AND WHERE IN THE 2ND FLOOR WILL FIRE SPRINKLERS BE
 PLACED. WILL HERE BE COVERED DINING AREAS ON THE 2ND
 FLOOR.
  
 2D)(1) PLEASE NOTE THE OCCUPANT LOAD AS SHOWN ON THE 2
 COVERSHEET IS CURRENTLY LISTED AT 496 OCCUPANTS. WITH
 ANY ADDITIONAL OCCUPANT LOADING EITHER THE 7 SQ. FT./
 OCCUPANT OR THE 5 SQ. FT. / OCCUPANT THIS WILL PUT YOU
 OVER 500 OCCUPANTS CREATING A THRESHOLD BUILDING.
 PLEASE NOTE IF THE OCCUPANT LOAD CAN BE KEPT AT UNDER
 500 OCCUPANTS THEN COMMENT 3 GOES AWAY. IF COMMENT 3
 (3A-3I) GOES AWAY THEN ALL STEEL WORK WILL NEED TO BE
 INSPECTED BY A 3RD PARTY, THE BUILDING DEPARTMENT WOULD
 HANDLE ALL OTHER STRUCTURE/ BUILDING INSPECTIONS.
  
 WELDED OR BOLTED CONNECTIONS. THIS BUILDING CONTAINS
 EITHER BOLTED AND OR WELDED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 2D)(2) PLEASE ALSO CONSIDER IF THE OCCUPANT LOAD IS 500
 OR LESS THAN ONLY 2 EXITS ARE REQUIRED. IF THE OCCUPANT
 LOAD IS OVER 500 THEN 3 VERTICAL EXITS WOULD BE
 REQUIRED. SEE THE 2017 FBC-B TABLE 1006.3.1.
  
 3) THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 3G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
 4) PLEASE NOTE THE PROPOSED DEMOLITION PLAN & LIFE
 SAFETY SHOWS NEW DOOR OPENINGS ON THE EAST SIDE OF THE
 BUILDING WHICH ARE WITHIN ONE FOOT OF THE PROPERTY LINE
 AND NEW OUTSWING DOORS THAT TRANSGRESS OVER THE
 PROPERTY LINE. PLEASE REVIEW IN THE 2017 FBC-B TABLE
 705.8 0-33 FEET FROM THE PROPERTY LINE (SPRINKLERED) NO
 OPENINGS ARE PERMITTED.
 5A) PLEASE NOTE FOR THE LIFE SAFETY PLAN ALSO MISSING
 IS THE REQUIREMENT THAT A 1-HOUR FIRE RATING IS
 REQUIRED FOR EXTERIOR WALLS BASED ON THE IRE SEPARATION
 DISTANCE FOR 0-5 FEET FROM THE PROPERTY LINE SEE TABLE
 602 OF THE FBC-B.
 5B) PLEASE NOTE WHEN YOU LOOK AT GEO NAV COUNTY ARIAL
 MAPS TO THE EAST AND WEST ARE STEPPED BUILDINGS BOTH A
 BIT HIGHER THAN THE PARAPET OF 522 WITH WINDOWS IN EACH
 BUILDING AT THE PROPERTY LINE. THE EAST BUILDING DOES
 HAVE A WINDOW WELL SECTION THAT STEPS BACK 5 FEET
 HORIZONTAL DISTANCE FROM THE PROPERTY LINE. PLEASE
 PROVIDE IF THESE BUILDINGS HAVE AREAL RIGHTS OVER 522
 IF NOT THEN YOU WILL NEED TO SHOW COMPLIANCE WITH 2020
 FBC-BUILDING SECTIONS:
 706.6.1 STEPPED BUILDINGS.
 706.7 COMBUSTIBLE FRAMING IN FIRE WALLS.
 706.8. OPENINGS.
  
 6) THE PROPOSED DEMO PLAN FOR THE 1ST FLOOR SHOWS THE
 REMOVAL OF MOST OF THE 1ST FLOOR SLAB. HAS THIS BEEN
 VERIFIED THAT THIS IS STEM WALL CONSTRUCTION, OTHERWISE
 YOU WILL LOSE THE EXTERIOR WALL ELEMENTS? 102.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 7A) THE LIFE SAFETY PLAN DOES NOT SHOW IN THE BUILDING
 DATA LIVE LOAD INFORMATION FOR ASSEMBLY AREA FLOOR
 LOADING, NEW STAIRS AND EXITS, HANDRAILS AND GUARDS.
 2017 FBC-B TABLE 1607.1.
 7B) THE LIFE SAFETY PLAN DOES NOT INCORPORATE INTO THE
 BUILDING DATA THE BUILDING RISK CATEGORY FACTOR SINE
 THERE IS AS SHOWN NOW 496 OCCUPANTS. NEITHER DOES THE
 S-1 SHEET IDENTIFY THE BUILDING RISK CATEGORY FACTOR.
 THE S-1 SHEET DOES IDENTIFY THE VULT WIND SPEED OF 170
 MPH, 3 SECOND GUST. PLEASE REVIEW THE 2017 FBC-B TABLE
 1604.5 RISK CATEGORY III. BUILDINGS AND OTHER
 STRUCTURES WHOSE PRIMARY OCCUPANCY IS PUBLIC ASSEMBLY
 WITH AN OCCUPANT LOAD OF GREATER THAN 300 HAS A RISK
 CATEGORY III. PLEASE REVIEW IN THE 2017 FBC-B FIGURE
 1609.3(2) OR 180 MPH VULT.
  
 8A) SHEET S-1 STATES THE PLANS WERE DESIGNED UNDER THE
 2017 FBC-B AND ASCE 7-10 AND ALTERATION LEVEL 2. PLEASE
 UPDATE THE CODES TO 2017 FBC-B ASCE 7-10, RICK CATEGORY
 III/ 180 MPH VULT AND ALTERATION LEVEL III, AND NEW
 VERTICAL ADDITION UNDER THE 2017 EXISTING BUILDING CODE
 SECTION 1103.2. NOTE THERE IS NO EXPOSURE CATEGORY
 GIVEN.
  
 8B) WITH THE BUILDING RISK CATEGORY CHANGED THE WIND
 DESIGN PRESSURES FOR THE COMPONENTS AND CLADDING WILL
 ALSO BE AFFECTED AND INCREASED. TO 2017 FBC-B ASCE
 7-10, RICK CATEGORY III/ 180 MPH VULT.
  
 8C) NOTE, DEPENDING ON THE OUTCOME OF 2D & 3 THIS MAY
 BE CONSIDERED A THRESHOLD BUILDING. THIS DETERMINATION
 SHOULD BE MADE BY THE NEXT REVIEW CYCLE.
  
 9A) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 9C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9D) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 10) THE LS-1 LIFE SAFETY PLAN NOR SHEET A-8.0 STAIR
 PLAN SHOW WHAT THE TRAVEL DISTANCE IS FOR THE NEW FRONT
 STAIRWAY ( EXIT ACCESS STAIRWAY) ON THE 2ND FLOOR DOWN
 THE STAIRS (PARALLEL TO STAIRS) AND DISTANCE TO THE
 FRONT ENTRY/ EXIT DOOR. PLEASE DEMONSTRATE COMPLIANCE
 WITH TABLE 1017.2 AND SECTION 1017.3.1 EXIT ACCESS
 STAIRWAYS OF THE 2017 FBC-B.
  
 11A) SHEET A-8.0 STAIR PLANS IN THE BOTTOM RIGHT CORNER
 INDICATES THE RISERS ARE TO BE 7 INCHES PLUS, PLEASE
 NOTE SECTION 1011.5.2 RISER HEIGHT IS TO BE BETWEEN 4
 INCHES MINIMUM TO 7 INCHES MAXIMUM.
  
 11B) THE LEFT SIDE OF THIS SHEET, (CIRCLED) THE GUARD
 AND HANDRAIL ARE DRAWN WRONG THEY STOP ON TOP OF THE
 FIRST TREAD THEY DO NOT GO TO THE LANDING, BOTH THE
 HANDRAIL AND GUARD WOULD BE TOO HIGH, ESPECIALLY THE
 HANDRAIL. SEE 114.2 HEIGHT. SEE CIRCLED RED LINE
 DRAWING.
  
 12A) PLEASE REVIEW THE D-1.0 DEMO SHEET. THE PLAN SHOWS
 THE PROPOSED ELECTRICAL ROOM TO HAVE A PORTION OF THE
 WALL REMOVED. THE LIFE SAFETY SHEET SHOWS A NEW STAIR
 AND DOORWAY GOING TO THE ELECTRICAL ROOM. THERE IS A
 SECOND STAIRWAY THAT IS LEADING FROM THE ROOF LEVEL AND
 ENDING WITHIN THE COURTYARD, IT APPEARS TO BE AN OPEN
 OR EXTERIOR STAIRWAY. SHEET A-8.0 DETAIL # 2 SHOWS THE
 ELECTRICAL DOOR DIRECTLY BENEATH THE OPEN STAIRS
 LEADING FROM THE ROOF. SECTION 1027.6 EXTERIOR EXIT
 STAIRWAY PROTECTION. THE STAIRWAY SHALL BE SEPARATED
 FROM THE INTERIOR OF THE BUILDING AS REQUIRED IN
 SECTION 1023.2.
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EGRESS
 FROM NORMALLY OCCUPIED SPACES, THIS WOULD NOT BE AN
 ELECTRICAL ROOM.
  
 12B) THIS SAME DETAIL # 2 IS ADJACENT TO THE PROPERTY
 LINE. THIS DETAIL DOES NOT SHOW COMPLIANCE WITH
 1027.5(1) ADJACENT LOTS.
  
 12C) THE LS-1 SHEET 1ST FLOOR OUTSIDE DINING AREA SHOWS
 IT IS AN ENCLOSED COURTYARD. SINCE THIS IS CONSIDERED A
 COURTYARD THE OCCUPANT LOAD OF THE COURTYARD AND 1ST
 FLOOR ARE TO BE COMBINED TO SHOW THE TOTAL NUMBER OF
 OCCUPANTS LEADING THROUGH THE BACK GATES AND LEADING TO
 THE PUBLIC WAY. SHOW COMPLIANCE WITH 1004.5 OUTDOOR
 AREAS OF THE 2017 FBC-B.
  
 13) SHEETS A-3.0, MEP 3.4 & MEP3-4.1 ALL SHOW
 MECHANICAL EQUIPMENT ON TOP OF THE EXISTING ROOF. THERE
 ARE NO DETAILS FOR THE ROOF TOP PENETRATIONS THROUGH
 THE TWIN T?S NOR HOW TO TIE DOWN THE CURBING OR ROOFTOP
 EQUIPMENT, AIR HANDLERS, INTAKE AND EXHAUST VENTS AND
 OR RACKS AND STANDS.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 THE ROOF TOP A/C STAND PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW)
 OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND,
 THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS,
 WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL
 IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 14) SHEET MEP3-4.1 ON THE AIR COMPRESSOR TO RACK STATES
 THE WINDS TO WITHSTAND 170 MPH. PLEASE CHANGE SINCE THE
 RISK FACTOR IS AN III MEETING THE 180 VULT WIND DESIGN.
  
  
 15) THE LIFE SAFETY PLANS DO NOT SHOW ANY ACCESSIBLE
 FEATURES FOR SEATING, COUNT OF SEATS, NOR BAR TOP
 MODIFICATIONS FOR ACCESSIBLE SEATING. THE LIFE SAFETY
 SHEET DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE.
 15A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 15B) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 15C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 15D) 902.1 DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 15E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 15E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 16) I MIGHT OF MISSED THE PLAN BUT I DID NOT SEE
 ARCHITECTURAL SHEETS WITH THE RESTROOM CONFIGURATIONS,
 AND DETAILS FOR ACCESSIBLE ELEMENTS WITHIN THE REST
 ROOMS NOR COMPLIANCE WITH THE 2020 ACCESSIBILITY CODE.
  
 17) I MIGHT OF MISSED THE PLAN BUT I DID NOT SEE
 ARCHITECTURAL SHEETS WITH THE RESTROOM FINISHES AND
 COMPLIANCE WITH
 2017 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN RESTROOMS & SERVICE SINK AREAS EPOXY PAINT
 IS NO LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT
 SURFACE.
  
 17A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 17B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 17C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 18) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE
 REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA
 PROJECT DOX UPON NOTIFICATION BY THIS OFFICE.
 NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL
 FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT
 (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT
 FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE
 FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN
 BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT
 ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 19) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  