Plan Review Notes
Plan Review Notes For Permit 20111065
Permit Number 20111065
Review Stop G
Sequence Number 1
Notes
Date Text
2020-12-02 09:35:2112/02/20 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING TANK-LESS GAS ON STRUCTURE, THERE WAS A PERMIT
 IN 2007 FOR A 35 BTU?S HEATER IN SHED AND A 30 BTU?S
 BBQ. A FULL EVALUATION OF ALL GAS EQUIPMENT WILL BE
 NEEDED AT THIS TIME. PLEASE PROVIDE THE FOLLOWING ITEM.
  
 2. GAS RISER DIAGRAM REQUIRED PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER THE 2017 FBC
 RES. SECS. G2413.4.1, G2413.4.2.
  
 4. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR PER THE 2017 FBC RES. SEC.
 G2420.4.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER THE 2017 FBC FG SEC. 402.2 OR 2017 FBC
 RES. SEC. G2413.2.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR TANK-LESS ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH 2017 FBC FG
 SEC.305.1 OR 2017 FBC RES. SEC. G2408.1.
  
 8. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC RES.
 SECS. G2413.3, G2413.4, AND TABLES G2413.4 (1) THROUGH
 G2413.4 (21).
  
 9. SUBMIT THE SIZING TABLE USED IN THE DESIGN FOR THE
 GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS
 LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER
 STANDARD THAT WERE USED IN THE DESIGN OF THIS SYSTEM
 PER THE 2017 FBC RES. SEC. G2413.3.
  
 10. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF
 EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017
 FBC FG SEC 410.2.
  
 11. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER
 THE 2017 FBC RES. SEC. G2401.1.3.
  
 12. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2017 FBC
 RES. SEC. G2419.2.
  
 13. PLEASE REFER TO THE SPECIFICATION ON THE TANK-LESS
 AS IT SHOWS A WINDOW ABOVE, GIVE THE LOCATION AND
 DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION
 TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER
 SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 14. IF TANK-LESS REQUIRES CONDENSATE DRAIN IT BE 1'
 AWAY FROM STRUCTURE PER THE 2017 FBC SEC R318.5.
  
 15. WATER PIPES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE
 403.5.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  