Date |
Text |
2020-12-01 12:22:00 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected] AND REQUEST |
| THAT IT BE CONVERTED TO PROJECTDOX. |
| |
| 1. FBC B 107.1 FS 481.229 ( C ) BUILDINGS INTENDED FOR |
| PUBLIC USE; PLANS REQUIRE PREPARATION BY A REGISTERED |
| DESIGN PROFESSIONAL. PROVIDE A COMPLETE SET. |
| 2. FBC B 107.2.1. PROVIDE A LEGIBLE PLAN TO PROVIDE THE |
| FOLLOWING INFORMATION: TOTAL NUMBER OF PARKING SPACES; |
| NUMBER OF ACCESSIBLE SPACES; LOCATION OF ACCESSIBLE |
| ENTRANCES; SHOW ACCESSIBLE ROUTE FROM PUBLIC WAY; |
| ACCESSIBLE ROUTE FROM ACCESSIBLE SPACE TO ACCESSIBLE |
| ENTRANCE. |
| 3. FBC A 502.3. WHERE THE ACCESSIBLE ROUTE MUST CROSS |
| VEHICULAR TRAFFIC LANES, MARKED CROSSINGS ENHANCE |
| PEDESTRIAN SAFETY; PLEASE INDICATE LOCATION ON PLAN. |
| 4. FBC A 208.2.1. THE FOLLOWING USES HAVE ADDITIONAL |
| PARKING REQUIREMENTS: HOSPITAL OUTPATIENT FACILITIES; |
| REHABILITATION FACILITIES; OUTPATIENT PHYSICAL THERAPY |
| FACILITIES. PLAN IS TO EITHER SHOW LOCATION OF TENANTS |
| WITH ANY OF THE ABOVE USES OR PLAN IS TO INCLUDE A |
| STATEMENT WHICH STATES THAT NONE OF THE ABOVE USES |
| (HOSPITAL OUTPATIENT FACILITIES, REHABILITATION |
| FACILITIES, OUTPATIENT PHYSICAL THERAPY FACILITIES) ARE |
| AT THIS LOCATION. |
| |