Plan Review Notes For Permit 20111036 |
Permit Number |
20111036 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-25 14:04:10 | BUILDING REVIEW COMMENTS FOR REVISED DRAWINGS TO COMPLY | | WITH PROVISO: | | | | 1- SHEET A4.2: | | A)OK. | | | | B)DETAIL #16 RAMP AND STAIR DETAILS: NEED TO SHOW THE | | TOP AND BOTTOM EXTENSION AT RAMP. AND PROVIDE DETAILS. | | SEC. 505.10.1 FBC-ACCESSIBILITY. | | | | RESPONSE: | | SEMI COMPLIED. RAMP SHOWS TOP AND BOTTOM EXTENSIONS BUT | | DETAILS WERE NOT PROVIDED. | | | | C)DETAIL #14 AND DETAIL #17: THE BOTTOM EXTENSION AT | | STAIRS NEED TO EXTEND AT THE SLOPE OF THE STAIR FLIGHT | | AS REQUIRED BY SEC. 505.10.3 FBC-ACCESSIBILITY. | | | | RESPONSE: | | DETAIL #17 WAS REVISED BUT DETAIL #14 WAS NOT. ALSO, | | THE EXTENSION SHALL RETURN TO A WALL, GUARD, OR THE | | LANDING SURFACE AS REQUIRED BY SEC. 505.10.3 | | FBC-ACCESSIBILITY. REVISE AS REQUIRED. | | NOTE: REVISE DETAIL #22 ON SHEET A4.3 ALSO TO AVOID | | CONFLICTS/DELAYS. | | | | 2- OK. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|