2020-12-28 17:25:30 | 12/28/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 2. PLEASE PROVIDE A SPECIFICATION FOR THE SHOWER |
| COMPARTMENT THAT YOU ARE INSTALLING THAT HAS A |
| NARRATIVE AND A CODING STANDARD THAT CONFORM TO ASME |
| A112.19.2/CSA B45.1 OR CSA B45.5/IAPMO Z124 PER THE |
| 2017 FBC SEC. P 417.1 APPROVAL. |
| |
| 3. PLEASE ADDRESS FIRE COMMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |