Plan Review Notes
Plan Review Notes For Permit 20111031
Permit Number 20111031
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-12-18 12:50:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION THAT ALL FIRE RATED WALL WILL
 BE RESTORED TO CODE. HOWEVER, THERE IS NO INDIACTION OF
 WHAT WAL(S)L WILL BE REMOVED/DAMAGED/AFFECTED.
  
 PLEASE INDICATE WHAT WALL(S) WILL BE AFFECTED AND
 PROVIDE THE LISTED FIRE RATED WALL DETAIL THAT IT WILL
 BE RECONSTRUCTED TO.
  
  
  
 2) THERE IS AN INDICATION OF A BATHROOM FLOOR PLAN;
 HOWEVER, THERE IS NO INDICATION OF WHERE THIS BATHROOM
 IS WITHIN THE UNIT.
  
 PLEASE PROVIDE AN OVERALL UNIT FLOOR PALN AND INDICATE
 WHICH BATHROOM IS AFFECTED.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  