Plan Review Notes For Permit 20111031 |
Permit Number |
20111031 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-12-30 09:36:55 | BATH RENOVATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE COMPLETE | | UNIT LAYOUT - POINT OUT WHICH WALLS ARE TENANT | | SEPARATION WALLS (FIRE RATED WALLS). (CAN BE HAND | | DRAWN) (PLEASE LABEL THE ROOMS). | | 2) PROVIDE DRAWING DETAILS OF FIBO WALL INSTALLATION. | | 3) SHOW THAT "FIBO" WALLS MEET THESE REQUIREMENTS - | | BUILDING IS A CONSTRUCTION TYPE I - WALLS SHALL BE OF | | NON-COMBUSTIBLE OR FIRE RETARDANT MATERIAL FBC 603.1 | | ALLOWABLE MATERIALS. | | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS | | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING | | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 | | THROUGH 603.1.3: | | | | 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: | | | | 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED | | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
|