Plan Review Notes
Plan Review Notes For Permit 20111031
Permit Number 20111031
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-30 09:36:55BATH RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE COMPLETE
 UNIT LAYOUT - POINT OUT WHICH WALLS ARE TENANT
 SEPARATION WALLS (FIRE RATED WALLS). (CAN BE HAND
 DRAWN) (PLEASE LABEL THE ROOMS).
 2) PROVIDE DRAWING DETAILS OF FIBO WALL INSTALLATION.
 3) SHOW THAT "FIBO" WALLS MEET THESE REQUIREMENTS -
 BUILDING IS A CONSTRUCTION TYPE I - WALLS SHALL BE OF
 NON-COMBUSTIBLE OR FIRE RETARDANT MATERIAL FBC 603.1
 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.