Plan Review Notes For Permit 20111005 |
Permit Number |
20111005 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-12-03 12:42:31 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | ALTERNATE: CONTACT PETER VALENTI (561) 805-6673 | | [email protected] | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND | | SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR | | PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL | | LIMITATIONS #5.7 PAGE 5 OF THE EVALUATION REPORT OF | | PRODUCT APPROVAL FL2533-R24. SYSTEM NO. LWC-50 MDP | | (PSF) -60.0 DO NOT MEET ZONE 3 REQUIREMENTS OF -78.0 | | (PSF). SECOND REQUEST. | | |
|