2020-12-22 09:49:21 | 12/22/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THESE ARE MULTI-FAMILY DWELLINGS. THE WATER USERS |
| WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| ASSEMBLY AT THE POINT OF DELIVERY THAT IS LEAD-FREE AND |
| A CURRENT YEAR CERTIFICATION PER THE CITY OF WEST PALM |
| CROSS UTILITIES DEPARTMENT AND THEIR CONNECTION CONTROL |
| PROGRAM. |
| |
| 2. A LICENSED CONTRACTOR MUST REQUIRE SUB PLUMBING AND |
| GAS PERMITS FOR THE SCOPE OF WORK PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| |
| 3. ON SHEET A-1; |
| A. THE PLUMBING ISOMETRIC SHOW TWO AIR ADMITTANCE |
| VALVE, THE SYSTEM MUST HAVE A VENT THROUGH THE ROOF. A |
| MINIMUM OF ONE STACK VENT OR VENT STACK EXTENDED TO THE |
| OUTDOORS TO THE OPEN AIR PER THE FBC SEC. P 918.7. SHOW |
| COMPLIANCE WITH THE PLANS. |
| |
| B. PLEASE SHOW DIMENSION BETWEEN FIXTURES INSTALLATION |
| TO CONFORM TO THE 2017 FBC SEC. R 2705.1 (5). |
| |
| C. HOT WATER LINES NOT IN CONDITION SPACE SHALL BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2017 FBC SEC. RE |
| 403.5.3. |
| |
| D. HOT GAS HEATER IF CONDENSATE NEEDS TO BE 1' AWAY |
| FROM STRUCTURE PER THE 2017 FBC SEC. R318.5. |
| |
| 4. PLEASE PROVIDE MANUFACTURES INSTALLATION INSTRUCTION |
| FOR TH GAS WATER HEATER PER THE WPB AMENDMENTS TO THE |
| FBC 107.2.1. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |