2020-12-22 11:12:22 | 12/22/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. CITY RECORDS SHOW AN EXISTING GAS SYSTEM AT THIS |
| PROPERTY. THE BTU LOAD OF THE CURRENT GAS SYSTEM MUST |
| BE ADDED TO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS SIZED CORRECTLY. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS PRESSURE IS 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| PER THE 2017 FBC R SECS. G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| |
| 2 INDICATE THE PLAN IN WHICH THE GAS CODE'S SIZING |
| TABLES ARE BEING USED FOR THE SYSTEM PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 3. THE TYPE OF PIPE MENTION IS NOT APPROVED TO BE |
| INSTALLED UNDERGROUND. YOU MAY USE TRAC PIPE OR PE FOR |
| UNDERGROUND AND CSST OR METAL PIPE ABOVE GROUND, SO |
| PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. GAS RISER DIAGRAM REQUIRED, SO PLEASE SUBMIT AN |
| ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL |
| CUT SECTIONS OF PIPE PER 2017 FBC RES. SECS. G2413.4.1, |
| G2413.4.2. |
| |
| 5. SHOW THE TYPE OF PIPE MATERIAL BEING USED, ALL PIPE |
| SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL OR TRAC PIPE TUBING (IF |
| APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| 6. A LICENSED CONTRACTOR MUST REQUIRE A SUB GAS PERMIT |
| FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 105.1. |
| |
| 7. TYPE OF GAS (LP OR NATURAL) PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 8. SHOW ALL MP (STEP-DOWN) REGULATORS' LOCATION. A |
| LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC RES. SEC. G2420.4. |
| |
| 9. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND OR SYSTEM PER THE 2017 FBC |
| RES. SEC. G2413.4.1. |
| |
| 10. IF THIS TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN |
| AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE BUILDING'S EXTERIOR SHALL BE APPROVED |
| FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. SEC. |
| G2421.1. |
| |
| 10. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER THE 2017 FBC RES. SEC. G2413.2. |
| |
| 11. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR GAS TANK-LESS TO VERIFY |
| COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| |
| 12. PLEASE SHOW ALL REGULATORS, UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE, DRIP LEG, LABEL SHUT OFF |
| VALVES WITH THEM LABELED PER THE 2017 FBC RES. SEC |
| G2421.2 |
| |
| 13. ON THE PLAN, PLEASE THE LOCATION OF THE TANK-LESS |
| WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS |
| TIME AND ADDRESS THE COMENTS ABOVE. THIS WILL HAVE THE |
| GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO |
| ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS |
| HEATER ( A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR |
| THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON |
| PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS |
| CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS |
| REVIEW, WHICH STANDS FOR NOT REQUIRED BUT, A SUB PERMIT |
| WON'T BE ISSUED UNIT A REVIEW IS DONE FOR THAT SUB |
| PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |