Plan Review Notes For Permit 20110839 |
Permit Number |
20110839 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-01-19 07:02:07 | PLAN REVIEW / BUILDING | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER BUILDING - PX3169 | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CODES IN EFFECT: | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | | | 2ND REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. LOCATION OF GENERATOR TO BUILDING OPENINGS SHALL BE | | 10 FEET PER R303.5.1 | | | | R303.5.1 INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. | | | | |
|