2021-01-07 13:19:312ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110733
 1/7/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW ARE MARKED AS
 PASSED OR FAILED. NOTES IN CAP LETTERS HAVE BEEN ADDED
 TO SOME COMMENTS FOR CLARIFICATION. THE REQUESTED
 NARRATIVE WHICH WOULD HELP EXPEDITE THE PLUMBING PLAN
 REVIEW PROCESS WAS NOT SUBMITTED. PLEASE PROVIDE A
 WRITTEN RESPOPNSE TO THE COMMENTS.
  
 1) FAILED. PROVIDE PLUMBING PLANS AND SPECIFICATIONS. A
 THOROUGH REVIEW CANNOT BE ACCOMPLISHED WITH THE
 FOLLOWING DETAILS, DRAWINGS, SPECIFICATIONS AND
 INFORMATION ON THE PLANS: INCOMPLETE RESPONSES-SEE
 BELOW.
  
 A) PASSED. CODE COMPLIANCE DATA: PROVIDE A LIST OF
 CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE
 PROJECT- SECTION 107.2.1 WPB.
  
 B) FAILED. COMPLIANCE METHOD PER THE FLORIDA EXISTING
 BUILDING CODE- SEE SECTION 301.3 FBC EX.
  
 C) FAILED. OCCUPANCY CLASSIFICATION- CHAPTER 3 FBC B.
  
 D) FAILED. OCCUPANCY LOAD CALCULATIONS- TABLE 1004.5
 FBC B.
  
 E) FAILED. PLUMBING FIXTURE CALCULATIONS PER TABLE
 403.3 FBC P. PROVIDE A SCHEDULE OF REQUIRED AND
 PROVIDED PLUMBING FIXTURES- SECTION 107.3.5.1.3 WPB.
  
 F) FAILED. SANITARY AND WATER RISER LAYOUT AND RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB. SANITARY RISER
 DRAWING PROVIDED ONLY FOR UNIT 612.
  
 G) PASSED. WATER SERVICE AND BACKFLOW PREVENTION-
 SECTION 603.1 & 604.1 FBC P, & SECTION 107.3.5.1.3 WPB.
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR WATER
 SERVICE BACKFLOW PREVENTERS- SECTION 105.1 & 107.2.1
 WPB. WATER SERVICE NOW SHOWN AS EXISTING AND NO NEW
 BACKFLOW PREVENTER. A REDLINE NOTE WILL BE ADDED TO
 APPROVED PLANS.
  
 H) FAILED. WATER HEATERS AND HOT AND TEMPERED WATER
 SYSTEMS- SECTION 107.3.5.1.3 WPB, AND SECTIONS 502.1 &
 607.1 FBC P. REQUIRED TEMPERED WATER FOR LAVATORY NOT
 PROVIDED- SECTION 416.5 FBC P.
  
 I) FAILED. PLUMBING FIXTURE SCHEDULES- SECTION
 107.3.5.1.3 WPB, AND SECTION 405 FBC P. ACCESSIBLE
 PLUMBING FIXTURES MAY BE SELECTED "BY OWNER" AS NOTED
 ON THE PLAN HOWEVER THEY SHALL BE DESIGNATED AS
 DEFERRED SUBMITTALS REQUIRING APPROVAL BY THE DESIGN
 PROFESSIONALS- SECTION 107.3.4.1 WPB.
  
 J) PASSED. PLUMBING PIPING AND INSULATION
 SPECIFICATIONS- SECTION 107.3.5.1.3 WPB.
  
 L) FAILED. ACCESSIBILITY DETAILS AND DRAWINGS IN
 ACCORDANCE WITH SECTIONS 211, 212, 213, AND CHAPTER 6
 FBC ACC. SEE REQUIRED DETAILS LIST BELOW UNDER NEW
 COMMENT #5.
  
 2) DEFERRED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB. THE PLUMBING SUB-PERMIT APPLICATION
 SHALL BE SUBMITTED AND ONSITE PRIOR TO COMMENCEMENT OF
 PLUMBING WORK. A REDLINE NOTE WILL BE ADDED TO APPROVED
 PLANS.
  
 3) DEFERRED PLEASE NOTE SEPARATE PERMITS ARE REQUIRED
 FOR GAS PIPING, IRRIGATION SYSTEM, AND WATER SERVICE
 BACKFLOW PREVENTERS- SECTIONS 105.1 & 107.2.1 WPB. A
 REDLINE NOTE WILL BE ADDED TO APPROVED PLANS FOR
 IRRIGATION. THE PLANS DO APPEAR TO INDICATE NEW GAS
 PIPING OR BACKFLOW PREVENTERS.
  
 NEW COMMENTS.
  
 1) SHEET P2: PROVIDE SANITARY ISOMETRIC DRAWINGS FOR
 UNITS 614, 616, 618, AND 620- SECTION 107.3.5.1.3 WPB.
  
 2) P1.0, P1.1, P2.0: PROVIDE FULL OPEN SHUTOFF VALVES
 FOR THE WATER DISTRIBUTION SUPPLY PIPES AT THE
 ENTRANCES OF EACH UNIT- SECTION 606.1(2) FBC P.
  
 3) P1.0, P1.1, P2.0: INDICATE TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES USING A TEMPERATURE LIMITING
 DEVICE (MIXING VALVE) IN ACCORDANCE WITH SECTIONS 416.5
 & 617.2.1 FBC P.
  
 4) P2.0: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR THE NEW
 WATER HEATERS INDICATING MAKES, MODELS, AND EFFICIENCY
 RATINGS- TABLE C404.2 FBC EC.
  
 5) ACCESSIBLE PLUMBING FIXTURE DETAILS- FBC 17 ACC:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4
 H) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
 SHOWERS-TRANSFER TYPES.
 L) SHOWER DIMENSIONS- SECTION 608.2.1.
 M) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.1
 N) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1
 O) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
 P) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
 SHOWER- ROLL IN TYPES.
 Q) SHOWER DIMENSIONS- SECTION 608.2.2.
 R) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SECTION 608.2.2.1
 S) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3.2 AND
 609.4.
 T) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.2 & 608.6.
 U) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6.
  
 6) PROVIDE ENLARGED SHOWER PAN AND THRESHOLD
 INSTALLATION DETAILS IN ACCORDANCE WITH SECTION 417.3-
 417.5.2 FBC P, AND SECTION 608.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE NOTE THAT ADDITIONAL PLUMBING
 COMMENTS MAY OCCUR AFTER THE PLANS ARE SUBMITTED AND
 REVIEWED.
  