Plan Review Notes
Plan Review Notes For Permit 20110733
Permit Number 20110733
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-24 09:47:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110733
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT SEPARATE MECHANICAL PERMITS FOR EACH
 BUILDING. FBC 107.2
  
 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR EACH BUILDING. FBC EC R403.7.1
  
 3) PLEASE SHOW THE ANCHORAGE DETAILS OF THE CONDENSING
 UNIT FOR EACH BUILDING. FBC RES M1307.2
  
 4) PLEASE SHOW CONDENSATE REMOVAL FOR EACH BUILDING.
 FBC RES M1411.3
  
 5) PLEASE PROVIDE SPECIFICATIONS FOR THE BATHROOM
 EXHAUST FANS AND SHOW THE EXHAUST TERMINATION LOCATION.
 FBC RES TABLE M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  