2020-11-24 09:47:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20110733 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE SUBMIT SEPARATE MECHANICAL PERMITS FOR EACH |
| BUILDING. FBC 107.2 |
| |
| 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS FOR EACH BUILDING. FBC EC R403.7.1 |
| |
| 3) PLEASE SHOW THE ANCHORAGE DETAILS OF THE CONDENSING |
| UNIT FOR EACH BUILDING. FBC RES M1307.2 |
| |
| 4) PLEASE SHOW CONDENSATE REMOVAL FOR EACH BUILDING. |
| FBC RES M1411.3 |
| |
| 5) PLEASE PROVIDE SPECIFICATIONS FOR THE BATHROOM |
| EXHAUST FANS AND SHOW THE EXHAUST TERMINATION LOCATION. |
| FBC RES TABLE M1507.4 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |