2021-03-26 16:29:09 | 3RD REVIEW FBC-2020 MECHANICAL |
| PERMIT-20110707 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: APPROVED WITH THE FOLLOWING |
| PREVISO: NOTE (5) OF THE MECHANICAL REVIEWER?S COMMENTS |
| WILL NEED TO BE ADDRESSED BY 04/09/2021 |
| |
| 1) AS OF THIS DATE (03-26-2021) THERE HAVE BEEN NO |
| MECHANICAL PERMITS PULLED FOR THE MECHANICAL SYSTEMS |
| FOR THIS PROJECT. |
| |
| 2) CHRIS COLE?S COMMENT ON 04/22/2019: 1) IN ACCORDANCE |
| WITH THE ARCHITECT'S NARRATIVE, THE KITCHEN COOKING |
| APPLIANCES AND EQUIPMENT, THE KITCHEN HOODS AND FIRE |
| SUPPRESSION SYSTEMS WILL BE DONE UNDER SEPARATE PERMIT. |
| AS A RESULT, THE NARRATIVE INDICATES GAS-FIRED COOKING |
| APPLIANCE SUBMITTALS, COMBUSTION AIR CALCULATIONS, AIR |
| BALANCE CALCULATIONS, AND MAKE UP AIR TEMPERATURE |
| COMPLIANCE WILL ALSO BE DEFERRED TO A FUTURE DATE. |
| PLEASE PLACE LARGE BOLD NOTES ON THE PLAN TO INDICATE |
| THIS FOR PUBIC RECORD AND FOR THE CONTRACTORS IN THE |
| FIELD. |
| |
| 3) KITCHEN HOODS AND EQUIPMENT MUST BE SUBMITTED |
| SEPARATELY FOR REVIEW AND PERMITTING. HOOD PLANS HAVE |
| BEEN LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION. |
| PLEASE CONTACT THE PERMIT LIBRARIAN AT |
| [email protected] TO HAVE THE HOOD SHEETS REMOVED |
| FROM THIS SUBMITTAL. |
| |
| 4) REFRIGERATION EQUIPMENT MUST BE SUBMITTED SEPARATELY |
| FOR REVIEW AND PERMITTING. REFRIGERATION PLAN HAS BEEN |
| LOCKED AND WILL NOT BE PRINTED WITH THIS VERSION. |
| PLEASE CONTACT THE PERMIT LIBRARIAN AT |
| [email protected] TO HAVE THE REFRIGERATION SHEET |
| REMOVED FROM THIS SUBMITTAL. |
| |
| 5) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE |
| OF SPACE IN THIS BUILDING. EXAMPLE: 1ST FLOOR HAS A BAR |
| AREA BESIDE OF THE DINING ROOM/LOUNGE IT SHOULD BE |
| CALCULATED AT 100 OCCUPANTS PER 1000 SQ FT. THE |
| VESTIBULE SHOULD BE COUNTED AS A LOBBY. THERE IS ALSO A |
| STAGE IN THIS AREA WHICH SHOULD BE COUNTED AS 70 |
| OCCUPANTS PER 1000 SQ.FT. THE 2ND FLOOR HAS A |
| LOBBY/PREFUNCTION AREA THAT NEEDS MORE OUTDOOR AIR THAN |
| A LOBBY. THE STAGE ON THE MEZZANINE SHOULD BE COUNTED |
| AS 70 OCCUPANTS PER 1000 SQ.FT.. THE RELAX AREA SHOULD |
| BE COUNTED AS PART OF THE LOBBY/PREFUNCTION AREA. THE |
| ROOF HAS A ROOF TOP BAR THAT ISN?T SHOWN AT ALL IN THE |
| OUTDOOR AIR CALCULATIONS. ONCE THESE AREAS HAVE CHANGED |
| THE AIR BALANCE SCHEDULES SHOULD BE UPDATED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |