2021-03-04 13:57:082ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20110707
 3/4/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDENTS TO THE FBC SIXTH EDITION
 2017
  
 PLAN REVIEW RESULTS: DENIED.
 BASED ON THE RESUBMITTED PLANS AND NARRATIVE RESPONSES,
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW.
 REMARKS IN CAP LETTERS HAVE BEEN ADDED FOR FURTHER
 CLARIFICATION.
  
 13) FAILED. P103 & P503: REFER TO SECTION 1107.1 FBC P
 AND VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM
 POSSIBLE DEPTH OF WATER THAT WILL POND THEREON AS
 DETERMINED BY THE RELATIVE LEVELS OF ROOF DECK AND
 OVERFLOW WEIRS, SCUPPERS, EDGES OR SERVICEABLE DRAINS
 IN COMBINATION WITH THE DEFLECTED STRUCTURAL ELEMENTS.
 IN DETERMINING THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL
 PRIMARY ROOF DRAINAGE MEANS SHALL BE ASSUMED TO BE
 BLOCKED. THE MAXIMUM POSSIBLE DEPTH OF WATER ON THE
 ROOF SHALL INCLUDE THE HEIGHT OF THE WATER REQUIRED
 ABOVE THE INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO
 ACHIEVE THE REQUIRED FLOW RATE OF THE SECONDARY
 DRAINAGE MEANS TO ACCOMMODATE THE DESIGN RAINFALL RATE
 AS REQUIRED BY SECTION 1106. THE NARRATIVE REFERENCES
 SHEETS A1.03A, A1.03B, & A1.03C. I WAS NOT ABLE TO
 LOCATE THE SHEETS IN THE SET, HOWEVER THE ROOF DRAINAGE
 PLANS ARE SHOWN ON SHEET A1.04. THE SHEET IS
 INCOMPLETE. REFER TO THE SCHEDULES ON THE PLANS AND
 LABEL THE 01. 02, 03, 04 AREAS ON THE PLANS, AND ALL
 ROOF DRAIN LOCATIONS ON FLAT ROOFS. PLEASE NOTE SOME DS
 LOCATIONS ARE NOT MARKED IN ACCORDANCE WITH MARKS SHOWN
 IN THE SCHEDULE.
  
 14) FAILED. P103, P104 & P503: PROVIDE SECONDARY OR
 EMERGENCY OVERFLOW ROOF DRAIN SYSTEMS INCLUDING
 CALCULATIONS AND OVERFLOW DRAIN DETAILS- SEE SECTION
 1108 FBC P. SEE COMMENT NOTES FOR #13.
  
 15) FAILED. P503: PROVIDE A CONDENSATE DISPOSAL RISER-
 SECTION 107.2.1 WPB. THE RISER IS INCOMPLETE AND DOES
 NOT INCLUDE ALL THE FAN COIL UNITS THROUGHOUT THE
 FLOORS.
  
 18) FAILED P501, SANITARY D: PROVIDE CLEANOUTS AT THE
 BASES OF THE 3 IN. STACKS. A) THE REVISION CLOUD IS
 BLOCKING THE TEXT OF NOTE 8. PLEASE PROVIDE THE CLOUD
 AROUND THE NUMBERS ONLY. B) ISO C: LABEL THE ISO AS
 GREASE WASTE ISOMETRIC AND LABEL THE GREASE WASTE LINE-
 GW. REMOVE THE HANDSINKS AND FLOOR SINK BY THE ICEMAKER
 AND ROUTE THE DRAINAGE TO THE SANITARY LINE. PLEASE SEE
 REMARKS UNDER NEW COMMENT #2 BELOW.
  
 19) FAILED. P601: PLEASE PROVIDE INDIRECT WASTE
 PLUMBING PIPING DETAILS FOR THE 2 AND 3-COMPARTMENT
 SINKS, THE DISHWASHER, AND ALL OTHER DISHWASHING SINKS
 AND FOOD HANDLING EQUIPMENT OR FIXTURES- REFER TO
 SECTIONS 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2
 FBC P. A MINIMUM 4 IN. AIR GAP IS REQUIRED FOR A 2 IN.
 WASTE PIPE- SECTION 802.2.1 FBC P.
  
 20) FAILED. P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR
 TO BE MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
 ALL OTHER FIXTURES FROM THE KITCHEN CONSULTANT LIST ARE
 INCLUDED IN THE SCHEDULE. PLEASE NOTE THAT THE
 3-COMPARTMENT SINK IS NOT IN THE KITCHEN SCHEDULE ON
 A4.04.
  
 21) FAILED. P701: ITEM #35 WHICH IS REFERENCED IN ITEM
 #36 & 37 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1
 WPB. SEE COMMENT # 20 REMARKS.
  
 25) FAILED. P-202, P403, P404 & P502: SHOW SHUTOFF
 VALVES FOR THE RISERS UP TO THE HOSE BIBS, BAR AND
 BATHROOMS- SECTION 606.1 FBC P. VALVES NOT SHOWN. NOTE
 112 IS REQUIRING AN IN-LINE BF PREVENTER FOR THE HOSE
 BIB. REFER TO SECTION - 608.15.4.2 HOSE CONNECTIONS.
 SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND OTHER OPENINGS
 WITH A HOSE CONNECTION SHALL BE PROTECTED BY AN
 ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A
 PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS.
  
 1) SHEETS P000, P101: LABEL THE GREASE WASTE LINE- (GW)
 AND THE SANITARY LINE- (SAN) PER THE SYMBOL LIST. THE
 GREASE WASTE IS MARKED ST AND MANY OF THE SANITARY
 LINES ARE NOT MARKED.
  
 2) P101, P401, A4.04: IN COMPLIANCWE WITH SECTION
 1003.3.1 FBC P, THE CHIEF PLUMBING INSPECTOR IS NOT
 PERMITTING HANDSINKS TO BE DRAINED INTO A GREASE
 INTERCEPTOR- PLEASE CORRECT THE PLANS SECTION 1003.3.1
 FBC P. THE PLAN ALSO SHOWS CLEAR WATER WASTE FROM FLOOR
 SINKS BY THE ICE MACHINE (K12) DRAINING INTO THE GREASE
 WATE LINE WHICH IS NOT PERMITTED. PLEASE ROUTE THE
 DRAINAGE FROM THESE FIXTURES TO THE SANITARY.
  
 2) P102: LABEL THE SAN DOWN IN THE CHASE.
  
 3) P103: LABEL THE SAN DOWN IN THE MEN'S AND WOMEN'S
 RESTROOMS.
  
 4) P401, DETAIL C: LABEL THE GREASE WASTE LINE- (GW)
 PER THE SYMBOL LIST. IT IS MARKED ST.
  
 5) P501: A) THE REVISION CLOUD IS BLOCKING THE TEXT OF
 NOTE 8. PLEASE PROVIDE THE CLOUD AROUND THE NUMBERS
 ONLY. B) ISO C; LABEL THE ISO AS GREASE WASTE ISOMETRIC
 AND LABEL THE GREASE WASTE LINE- GW. REMOVE THE
 HANDSINKS AND FLOOR SINK BY THE ICEMAKER AND ROUTE THE
 DRAINAGE FROM THESE FIXTURES TO THE SANITARY LINE.
  
 6) P701: EQUIPMENT SCHEDULES FOR TEA-1 AND TEA-2 ARE
 NOT PROVIDED. PLEASE NOTE THAT THERMAL EXPANSION TANKS
 SHALL BE INSTALLED ON THE WH COLD WATER INLET PIPE AT A
 POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE
 REDUCING VALVES AND BACKFLOW PREVENTERS.
  
 7) P701: IT IS ACKNOWLEDFGED THAT THE GREASE
 INTERCEPTOR SHALL BE SEPARATELY PERMITTED. COMPLETE
 PLANS, CALCULATIONS, AND PRODUCT SPECIFICATIONS SHALL
 BE SUBMITTED. PLEASE NOTE THAT THE CURRENT CALCULATIONS
 DO NOT INCLUDE THE 2-COMPARTMENT SINK, AND THE DRAINAGE
 FROM THE FLOOR SINKS SERVING COOKING APPLIANCES, AND
 THE TRENCH DRAIN.
  
 8) P702: PLEASE ADD A BACKFLOW PREVENTER FOR THE WATER
 FILTRATION SYSTEM FOR PROTECTION AGAINST CONTAMINATION-
 SECTION 608.3 FBC P.
  
 9) IRR-1: BACKFLOW PREVENTERS ARE REQUIRED TO PROTECT
 THE POTABLE WATER SYSTEM PER SECTION 608.1 FBC P. THE
 POTABLE WATER FOR THE BUILDING IS CITY SUPPLIED, AND
 THE IRRIGATION WATER IS WELL SUPPLIED. PLEASE CLARIFY
 THE NEEED FOR THE BF PREVENTER. IS IT FOR PROTECTION OF
 THE PUMP, THE WELL WATER?
  
 10) P-503: PLEASE SEE SEPARATE GAS REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER