Date |
Text |
2021-03-04 13:57:08 | 2ND REVIEW FBC-2017 PLUMBING |
| PERMIT- 20110707 |
| 3/4/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDENTS TO THE FBC SIXTH EDITION |
| 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| BASED ON THE RESUBMITTED PLANS AND NARRATIVE RESPONSES, |
| FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW. |
| REMARKS IN CAP LETTERS HAVE BEEN ADDED FOR FURTHER |
| CLARIFICATION. |
| |
| 13) FAILED. P103 & P503: REFER TO SECTION 1107.1 FBC P |
| AND VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM |
| POSSIBLE DEPTH OF WATER THAT WILL POND THEREON AS |
| DETERMINED BY THE RELATIVE LEVELS OF ROOF DECK AND |
| OVERFLOW WEIRS, SCUPPERS, EDGES OR SERVICEABLE DRAINS |
| IN COMBINATION WITH THE DEFLECTED STRUCTURAL ELEMENTS. |
| IN DETERMINING THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL |
| PRIMARY ROOF DRAINAGE MEANS SHALL BE ASSUMED TO BE |
| BLOCKED. THE MAXIMUM POSSIBLE DEPTH OF WATER ON THE |
| ROOF SHALL INCLUDE THE HEIGHT OF THE WATER REQUIRED |
| ABOVE THE INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO |
| ACHIEVE THE REQUIRED FLOW RATE OF THE SECONDARY |
| DRAINAGE MEANS TO ACCOMMODATE THE DESIGN RAINFALL RATE |
| AS REQUIRED BY SECTION 1106. THE NARRATIVE REFERENCES |
| SHEETS A1.03A, A1.03B, & A1.03C. I WAS NOT ABLE TO |
| LOCATE THE SHEETS IN THE SET, HOWEVER THE ROOF DRAINAGE |
| PLANS ARE SHOWN ON SHEET A1.04. THE SHEET IS |
| INCOMPLETE. REFER TO THE SCHEDULES ON THE PLANS AND |
| LABEL THE 01. 02, 03, 04 AREAS ON THE PLANS, AND ALL |
| ROOF DRAIN LOCATIONS ON FLAT ROOFS. PLEASE NOTE SOME DS |
| LOCATIONS ARE NOT MARKED IN ACCORDANCE WITH MARKS SHOWN |
| IN THE SCHEDULE. |
| |
| 14) FAILED. P103, P104 & P503: PROVIDE SECONDARY OR |
| EMERGENCY OVERFLOW ROOF DRAIN SYSTEMS INCLUDING |
| CALCULATIONS AND OVERFLOW DRAIN DETAILS- SEE SECTION |
| 1108 FBC P. SEE COMMENT NOTES FOR #13. |
| |
| 15) FAILED. P503: PROVIDE A CONDENSATE DISPOSAL RISER- |
| SECTION 107.2.1 WPB. THE RISER IS INCOMPLETE AND DOES |
| NOT INCLUDE ALL THE FAN COIL UNITS THROUGHOUT THE |
| FLOORS. |
| |
| 18) FAILED P501, SANITARY D: PROVIDE CLEANOUTS AT THE |
| BASES OF THE 3 IN. STACKS. A) THE REVISION CLOUD IS |
| BLOCKING THE TEXT OF NOTE 8. PLEASE PROVIDE THE CLOUD |
| AROUND THE NUMBERS ONLY. B) ISO C: LABEL THE ISO AS |
| GREASE WASTE ISOMETRIC AND LABEL THE GREASE WASTE LINE- |
| GW. REMOVE THE HANDSINKS AND FLOOR SINK BY THE ICEMAKER |
| AND ROUTE THE DRAINAGE TO THE SANITARY LINE. PLEASE SEE |
| REMARKS UNDER NEW COMMENT #2 BELOW. |
| |
| 19) FAILED. P601: PLEASE PROVIDE INDIRECT WASTE |
| PLUMBING PIPING DETAILS FOR THE 2 AND 3-COMPARTMENT |
| SINKS, THE DISHWASHER, AND ALL OTHER DISHWASHING SINKS |
| AND FOOD HANDLING EQUIPMENT OR FIXTURES- REFER TO |
| SECTIONS 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 |
| FBC P. A MINIMUM 4 IN. AIR GAP IS REQUIRED FOR A 2 IN. |
| WASTE PIPE- SECTION 802.2.1 FBC P. |
| |
| 20) FAILED. P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR |
| TO BE MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| ALL OTHER FIXTURES FROM THE KITCHEN CONSULTANT LIST ARE |
| INCLUDED IN THE SCHEDULE. PLEASE NOTE THAT THE |
| 3-COMPARTMENT SINK IS NOT IN THE KITCHEN SCHEDULE ON |
| A4.04. |
| |
| 21) FAILED. P701: ITEM #35 WHICH IS REFERENCED IN ITEM |
| #36 & 37 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 |
| WPB. SEE COMMENT # 20 REMARKS. |
| |
| 25) FAILED. P-202, P403, P404 & P502: SHOW SHUTOFF |
| VALVES FOR THE RISERS UP TO THE HOSE BIBS, BAR AND |
| BATHROOMS- SECTION 606.1 FBC P. VALVES NOT SHOWN. NOTE |
| 112 IS REQUIRING AN IN-LINE BF PREVENTER FOR THE HOSE |
| BIB. REFER TO SECTION - 608.15.4.2 HOSE CONNECTIONS. |
| SILLCOCKS, HOSE BIBBS, WALL HYDRANTS AND OTHER OPENINGS |
| WITH A HOSE CONNECTION SHALL BE PROTECTED BY AN |
| ATMOSPHERIC-TYPE OR PRESSURE-TYPE VACUUM BREAKER OR A |
| PERMANENTLY ATTACHED HOSE CONNECTION VACUUM BREAKER. |
| |
| NEW COMMENTS BASED ON RESUBMITTED PLANS. |
| |
| 1) SHEETS P000, P101: LABEL THE GREASE WASTE LINE- (GW) |
| AND THE SANITARY LINE- (SAN) PER THE SYMBOL LIST. THE |
| GREASE WASTE IS MARKED ST AND MANY OF THE SANITARY |
| LINES ARE NOT MARKED. |
| |
| 2) P101, P401, A4.04: IN COMPLIANCWE WITH SECTION |
| 1003.3.1 FBC P, THE CHIEF PLUMBING INSPECTOR IS NOT |
| PERMITTING HANDSINKS TO BE DRAINED INTO A GREASE |
| INTERCEPTOR- PLEASE CORRECT THE PLANS SECTION 1003.3.1 |
| FBC P. THE PLAN ALSO SHOWS CLEAR WATER WASTE FROM FLOOR |
| SINKS BY THE ICE MACHINE (K12) DRAINING INTO THE GREASE |
| WATE LINE WHICH IS NOT PERMITTED. PLEASE ROUTE THE |
| DRAINAGE FROM THESE FIXTURES TO THE SANITARY. |
| |
| 2) P102: LABEL THE SAN DOWN IN THE CHASE. |
| |
| 3) P103: LABEL THE SAN DOWN IN THE MEN'S AND WOMEN'S |
| RESTROOMS. |
| |
| 4) P401, DETAIL C: LABEL THE GREASE WASTE LINE- (GW) |
| PER THE SYMBOL LIST. IT IS MARKED ST. |
| |
| 5) P501: A) THE REVISION CLOUD IS BLOCKING THE TEXT OF |
| NOTE 8. PLEASE PROVIDE THE CLOUD AROUND THE NUMBERS |
| ONLY. B) ISO C; LABEL THE ISO AS GREASE WASTE ISOMETRIC |
| AND LABEL THE GREASE WASTE LINE- GW. REMOVE THE |
| HANDSINKS AND FLOOR SINK BY THE ICEMAKER AND ROUTE THE |
| DRAINAGE FROM THESE FIXTURES TO THE SANITARY LINE. |
| |
| 6) P701: EQUIPMENT SCHEDULES FOR TEA-1 AND TEA-2 ARE |
| NOT PROVIDED. PLEASE NOTE THAT THERMAL EXPANSION TANKS |
| SHALL BE INSTALLED ON THE WH COLD WATER INLET PIPE AT A |
| POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES, PRESSURE |
| REDUCING VALVES AND BACKFLOW PREVENTERS. |
| |
| 7) P701: IT IS ACKNOWLEDFGED THAT THE GREASE |
| INTERCEPTOR SHALL BE SEPARATELY PERMITTED. COMPLETE |
| PLANS, CALCULATIONS, AND PRODUCT SPECIFICATIONS SHALL |
| BE SUBMITTED. PLEASE NOTE THAT THE CURRENT CALCULATIONS |
| DO NOT INCLUDE THE 2-COMPARTMENT SINK, AND THE DRAINAGE |
| FROM THE FLOOR SINKS SERVING COOKING APPLIANCES, AND |
| THE TRENCH DRAIN. |
| |
| 8) P702: PLEASE ADD A BACKFLOW PREVENTER FOR THE WATER |
| FILTRATION SYSTEM FOR PROTECTION AGAINST CONTAMINATION- |
| SECTION 608.3 FBC P. |
| |
| 9) IRR-1: BACKFLOW PREVENTERS ARE REQUIRED TO PROTECT |
| THE POTABLE WATER SYSTEM PER SECTION 608.1 FBC P. THE |
| POTABLE WATER FOR THE BUILDING IS CITY SUPPLIED, AND |
| THE IRRIGATION WATER IS WELL SUPPLIED. PLEASE CLARIFY |
| THE NEEED FOR THE BF PREVENTER. IS IT FOR PROTECTION OF |
| THE PUMP, THE WELL WATER? |
| |
| 10) P-503: PLEASE SEE SEPARATE GAS REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |