2021-03-02 17:27:35 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-20110707 2ND CYCLE |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR THE |
| KITCHEN HOODS AND THE REFRIGERATION EQUIPMENT. |
| |
| |
| 1) PLEASE PROVIDE A LETTER SHOWING A CHANGE OF EOR. |
| |
| 2) SHEET M-501: PLEASE CHECK LABELING OF DUCTWORK FOR |
| DETAIL (2) AS IT APPEARS THE OUTDOOR AIR IS LABELED SA, |
| AND IT APPEARS THAT SA IS DUCTED INTO EACH RA. FBC |
| 107.2.1 |
| |
| 3) OUTDOOR AIR CALCULATIONS MUST BE CALCULATED |
| ACCORDING TO TABLE 403.3.1.1 NOT BY THE OCCUPANCY SHOWN |
| IN THE ARCHITECTURAL DRAWINGS. FBC M 403.3.1.1 |
| |
| 4) SHEET M-702: PLEASE PROVIDE A COMPLETE OUTDOOR AIR |
| CALCULATION CHART, THERE APPEARS TO BE SEVERAL SPACES |
| IN THIS BUILDING THAT DO NOT APPEAR IN THE VENTILATION |
| RATE CALCULATIONS. FBC M 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |