Plan Review Notes
Plan Review Notes For Permit 20110707
Permit Number 20110707
Review Stop M
Sequence Number 2
Notes
Date Text
2021-03-02 17:27:351ST REVIEW FBC-2020 MECHANICAL
 PERMIT-20110707 2ND CYCLE
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR THE
 KITCHEN HOODS AND THE REFRIGERATION EQUIPMENT.
  
  
 1) PLEASE PROVIDE A LETTER SHOWING A CHANGE OF EOR.
  
 2) SHEET M-501: PLEASE CHECK LABELING OF DUCTWORK FOR
 DETAIL (2) AS IT APPEARS THE OUTDOOR AIR IS LABELED SA,
 AND IT APPEARS THAT SA IS DUCTED INTO EACH RA. FBC
 107.2.1
  
 3) OUTDOOR AIR CALCULATIONS MUST BE CALCULATED
 ACCORDING TO TABLE 403.3.1.1 NOT BY THE OCCUPANCY SHOWN
 IN THE ARCHITECTURAL DRAWINGS. FBC M 403.3.1.1
  
 4) SHEET M-702: PLEASE PROVIDE A COMPLETE OUTDOOR AIR
 CALCULATION CHART, THERE APPEARS TO BE SEVERAL SPACES
 IN THIS BUILDING THAT DO NOT APPEAR IN THE VENTILATION
 RATE CALCULATIONS. FBC M 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  