Plan Review Notes
Plan Review Notes For Permit 20110707
Permit Number 20110707
Review Stop G
Sequence Number 2
Notes
Date Text
2021-03-04 15:17:061ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 20110707
 3/4/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P503 GAS ISOMETRIC:
  
 A) PLEASE LABEL THE REGULATORS AND SHOW THE OUTLET
 PRESSURES- SECTION 410.1 FBC FG. SUBMIT MANUFACTURER'S
 SPECIFICATIONS MARKED UP TO SHOW THE INLET AND OUTLET
 PRESSURE PIPE SIZES AND PRESSURES.
  
 B) SHOW THE LOCATION OF THE AUTO GAS VALVE FOR THE FIRE
 SUPPRESSION SYSTEM- SEC.10.4.1 NFPA 96.
  
 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING
 APPLIANCES- SECTION 304.1 FBC FG. INDICATE WHICH METHOD
 WILL BE USED TO SUPPLY THE AIR.
  
 3) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE FOR
 THE WATER HEATERS- SECTIONS 505 7 503 FBC FG.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES AND WATER HEATERS- SECTIONS 623.1 AND 624.1
 FBC FG. PLEASE INCLUDE THE SPECS FOR THE DIRECT VENT
 AIR INTAKE AND EXHAUST SYSTEM FOR THE WATER HEATER AS
 SHOWN ON SHEET M102.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  