2021-03-04 15:17:06 | 1ST REVIEW FBC-2017 FUEL GAS |
| PERMIT- 20110707 |
| 3/4/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P503 GAS ISOMETRIC: |
| |
| A) PLEASE LABEL THE REGULATORS AND SHOW THE OUTLET |
| PRESSURES- SECTION 410.1 FBC FG. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS MARKED UP TO SHOW THE INLET AND OUTLET |
| PRESSURE PIPE SIZES AND PRESSURES. |
| |
| B) SHOW THE LOCATION OF THE AUTO GAS VALVE FOR THE FIRE |
| SUPPRESSION SYSTEM- SEC.10.4.1 NFPA 96. |
| |
| 2) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| APPLIANCES- SECTION 304.1 FBC FG. INDICATE WHICH METHOD |
| WILL BE USED TO SUPPLY THE AIR. |
| |
| 3) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE FOR |
| THE WATER HEATERS- SECTIONS 505 7 503 FBC FG. |
| |
| 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| APPLIANCES AND WATER HEATERS- SECTIONS 623.1 AND 624.1 |
| FBC FG. PLEASE INCLUDE THE SPECS FOR THE DIRECT VENT |
| AIR INTAKE AND EXHAUST SYSTEM FOR THE WATER HEATER AS |
| SHOWN ON SHEET M102. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |