Plan Review Notes
Plan Review Notes For Permit 20110707
Permit Number 20110707
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-07 15:38:031ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110707
 12/7/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-000:
  
 A) PROVIDE A LIST OF SEPARATELY PERMITTED ITEMS
 INCLUDING THE WATER SERVICE BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, GAS PIPING, GENERATOR, AND THE IRRIGATION
 SYSTEM. PLEASE NOTE COMPLETE SETS OF PLANS AND
 SPECIFICATIONS ARE REQUIRED FOR REVIEW- SECTION 107.2.1
 WPB.
  
 B) PROVIDE A LIST OF DEFERRED SUBMITTALS INCLUDING THE
 FOOD SERVICE EQUIPMENT PLANS, AND ALL PLUMBING
 FIXTURES, APPLIANCES, DEVICES, AND EQUIPMENT
 SPECIFICATIONS NOT TO BE SUBMITTED UNDER THIS MAIN
 PERMIT- SECTION 107.3.4.1 WPB.
  
 2) THERE ARE TWO P-101 PLANS IN THIS SUBMITTAL- ONE
 FROM THE PREVIOUS ENGINEER AND ONE FROM THE NEW
 ENGINEER. PLEASE RENAME ONE OF THESE SHEETS- SECTION
 107.2.1 WPB.
  
 3) P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE
 THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES.
  
 4) P-001: THIS PLAN SHEET IS NOT IN THE INDEX ON P-000.
 PLEASE ADD IT TO THE INDEX AND REVISE THE FIXTURE AND
 EQUIPMENT SCHEDULES ON THE PLAN TO MATCH THE SCHEDULES
 ON P701- SECTION 107.2.1 WPB.
  
 5) SHEETS A0.04 & P101: PLEASE PROVIDE THE CIVIL, PLANS
 THAT ARE REFERENCED IN THE NOTES AND OTHER PLAN SHEET
 NOTES FOR CONTINUATIONS OF THE PLUMBING AND STORM DRAIN
 PIPING SYSTEMS- SECTION 107.2.1.
  
 6) ELLIS AND GRITTER P101: REVISE THE GREASE WASTE
 PIPING LAYOUT TO MATCH THE NEW LAYOUT SHOWN ON SHEETS
 P401 & 501- SECTION 107.2.1 WPB. BOTH THE OLD AND NEW
 P101 PLAN SHEETS AND P401 & P501 SHOW THE MOP SINK
 DRAIN CONNECTING TO THE GREASE WASTE LINE, PLEASE NOTE
 IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE MOP SINK
 SHALL DRAIN INTO THE SANITARY AND NOT INTO THE GREASE
 WASTE LINE.
  
 7) P101 & P701 GREASE INTERCEPTOR: AS NOTED IN COMMENT
 #1A A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE
 GREASE INTERCEPTOR, AND THE SUBMITTAL SHALL INCLUDE THE
 FOLLOWING LIST OF ITEMS.
  
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUAL FOR THE SCHIER INTERCEPTOR WITH APPROVAL STAMPS
 BY THE EOR.
  
 B) REVISED SIZING CALCULATIONS. PLEASE NOTE THE CURRENT
 EQUIPMENT SCHEDULE SEEMS TO INDICATE TWO DIFFERENT
 SIZING METHODS- THE PDI METHOD WHICH IS BASED ON GPM
 FLOW-THRU RATINGS AND GREASE RETENTION TIME FOR THE
 FIXTURES, AND FAC RULE 64E-6.013 METHOD WHICH IS BASED
 ON THE NUMBER OF SEATS, GALLONS OF WASTEWATER ETC.-
 THIS METHOD IS COMMONLY USED FOR GRAVITY-TYPE
 INTERCEPTORS.
  
 8) P101, P601. P701 SUMP PUMP AND PIT.
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP
 PUMP. SECTION 712.3.1 FBC P. THE PUMP SHALL BE EQUIPPED
 WITH AN OIL WATER SEPARATOR OR IT SHALL BE PROVIDED
 SEPARATELY- SECTION 1003.4 FBC P.
  
 B) PROVIDE THE DIMENSIONS OF THE SUMP PIT IN THE
 DETAIL- SECTION 712.3.2.
  
 C) PROVIDE A GAS TIGHT COVER FOR THE SUMP PIT- SECTION
 712.3.2.
  
 D) PROVIDE THE SIZE OF THE DISCHARGE PIPING AND PROVIDE
 A VENT FOR THE PIT- SECTION 713.2.1.
  
 9) P101 & P102: NOTE #8 (P102) INDICATES CLEANOUTS AT
 THE BASE OF SANITARY STACKS WHICH ARE NOT SHOWN ON AT
 THE CHASE LOCATION BY THE RESTROOMS. PLEASE NOTE THAT
 SECTION 1101.8 REQUIRES STORM DRAIN CLEANOUTS TO BE
 INSTALLED IN ACCORDANCE WITH THE CODES FOR SANITARY
 DRAIN CLEANOUTS.
  
 10) P103, NOTE 306: ACCORDING TO SECTION 1104.2 FBC P
 FLOOR DRAINS SHALL NOT BE CONNECTED TO STORM DRAINS.
 PLEASE PROVIDE MORE INFORMATION AND DETAILS TO CLARIFY-
 SECTION 107.2.1 WPB.
  
 11) P103: PROVIDE PRODUCT SUBMITTALS FOR RD-2, FD-1,
 AND TD-1. PLEASE CLARIFY IF THE FD-1 AND TD-1 SHOWN IN
 THE P701 SCHEDULE FOR THE INTERIOR ARE THE SAME TYPE OF
 FIXTURES TO BE INSTALLED IN THE EXTERIOR OPEN ROOF
 AREAS- SECTION 1105.1 FBC P AND SECTION 107.2.1 WPB.
  
 12) P103: FD-1 ON THE LOWER ROOF SHALL NOT CONNECT TO
 THE SANITARY PER SEC. 90-126 WPB CODE OF ORDINANCES.
  
 13) P103 & P503: REFER TO SECTION 1107.1 FBC P AND
 VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM POSSIBLE
 DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY
 THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS,
 SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION
 WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING
 THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF
 DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE
 MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL
 INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE
 INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE
 THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS
 TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY
 SECTION 1106.
  
 14) P103, P104 & P503: PROVIDE SECONDARY OR EMERGENCY
 OVERFLOW ROOF DRAIN SYSTEMS INCLUDING CALCULATIONS AND
 OVERFLOW DRAIN DETAILS- SEE SECTION 1108 FBC P.
  
 15) P503: PROVIDE A CONDENSATE DISPOSAL RISER- SECTION
 107.2.1 WPB.
  
 16) P401 SANITARY A: SEE COMMENT #7.
  
 17) P401, SANITARY C: IT APPEARS A CLEANOUT IS MISSING
 FOR THE 4 IN. GREASE WASTE BRANCH LINE IN THE KITCHEN
 BY THE DISHWASHER- SECTION 708.1.4 FBC P. CLARIFY HOW
 ACCESS TO THE WCO IN THE FREEZER WILL BE PROVIDED-
 SECTIONS 708.1.9 & 708.1.0 FBC P.
  
 18) P501, SANITARY D: PROVIDE CLEANOUTS AT THE BASES OF
 THE 3 IN. STACKS.
  
 19) P601: PLEASE PROVIDE INDIRECT WASTE PLUMBING PIPING
 DETAILS FOR THE 2 AND 3-COMPARTMENT SINKS, THE
 DISHWASHER, AND ALL OTHER DISHWASHING SINKS AND FOOD
 HANDLING EQUIPMENT OR FIXTURES- REFER TO SECTIONS
 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 FBC P.
  
 20) P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR TO BE
 MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
  
 21) P701: ITEM #35 WHICH IS REFERENCED IN ITEM #36 & 37
 IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB.
  
 22) P201: SHOW THE LOCATIONS OF THE WATER METER AND
 MAIN SHUT OFF VALVES- SECTION 606.1 FBC P.
  
 23) P201: SHOW FULL OPEN SHUT OFF VALVES FOR THE DOWN
 FEEDING WATER SUPPLY LINES BY JAN. 118- SECTION
 606.1(5) FBC P.
  
 24) P201: THERE APPEARS TO BE A SHUT OFF VALVE MISSING
 AT THE RISER BY DOOR 108- SECTION 606.1(4) FBC P.
  
 25) P-202, P403, P404 & P502: SHOW SHUTOFF VALVES FOR
 THE RISERS UP TO THE HOSE BIBS, BAR AND BATHROOMS-
 SECTION 606.1 FBC P.
  
 26) P-201, P202, P203, P403, P404, & P502: SHOW THE
 LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS, MIXING
 VALVES, AND BACKFLOW PREVENTERS- SECTIONS 604.9, 416.4,
 607.1.2, & 608.3 FBC P. PLEASE NOTE THAT BACKFLOW
 PREVENTERS ARE REQUIRED FOR WATER SUPPLY LINES TO THE
 DISHWASHER, ICE MAKERS, WATER FILTERING SYSTEM,
 CHEMICAL STORAGE CABINET, AND BEVERAGE AND COFFEE
 DISPENSERS ETC.
  
 27) P701: PLEASE LABEL THE LOCATION OF THE CHEMICAL
 STORAGE CABINET ON THE DOMESTIC PLANS AND RISER
 DRAWINGS- SECTION 608.3 FBC P. CLARIFY IF WASTE WATER
 FROM THE CABINET WILL BE DRAINING INTO THE SANITARY
 SYSTEM AND PROVIDE A NEUTRALIZING DEVICE IF APPLICABLE-
 SECTION 803.1 FBC P.
  
 28) P601: PLEASE PROVIDE A PLUMBING DIAGRAM FOR THE
 CHEMICAL STORAGE CABINET- SECTION 107.2.1 WPB.
  
 29) P701: PROVIDE THE EFFICIENCY RATINGS OF THE WATER
 HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 30) P701: PROVIDE DRAIN PANS AND DRAIN PAN LINES FOR
 THE WATER HEATERS- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 31) P701: PROVIDE A PLUMBING DEVICE SCHEDULE SHOWING
 THE MAKES AND MODEL NUMBERS AND LISTINGS OF THE WATER
 HAMMER ARRESTORS, BACKFLOW PREVENTERS, MIXING VALVES,
 AND TRAP PRIMERS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER