2020-12-07 15:38:03 | 1ST REVIEW FBC-2017 PLUMBING |
| PERMIT- 20110707 |
| 12/7/2020 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P-000: |
| |
| A) PROVIDE A LIST OF SEPARATELY PERMITTED ITEMS |
| INCLUDING THE WATER SERVICE BACKFLOW PREVENTER, GREASE |
| INTERCEPTOR, GAS PIPING, GENERATOR, AND THE IRRIGATION |
| SYSTEM. PLEASE NOTE COMPLETE SETS OF PLANS AND |
| SPECIFICATIONS ARE REQUIRED FOR REVIEW- SECTION 107.2.1 |
| WPB. |
| |
| B) PROVIDE A LIST OF DEFERRED SUBMITTALS INCLUDING THE |
| FOOD SERVICE EQUIPMENT PLANS, AND ALL PLUMBING |
| FIXTURES, APPLIANCES, DEVICES, AND EQUIPMENT |
| SPECIFICATIONS NOT TO BE SUBMITTED UNDER THIS MAIN |
| PERMIT- SECTION 107.3.4.1 WPB. |
| |
| 2) THERE ARE TWO P-101 PLANS IN THIS SUBMITTAL- ONE |
| FROM THE PREVIOUS ENGINEER AND ONE FROM THE NEW |
| ENGINEER. PLEASE RENAME ONE OF THESE SHEETS- SECTION |
| 107.2.1 WPB. |
| |
| 3) P-000: PROVIDE PLUMBING FIXTURE CALCULATIONS IN |
| COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A SCHEDULE |
| THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF |
| FIXTURES. |
| |
| 4) P-001: THIS PLAN SHEET IS NOT IN THE INDEX ON P-000. |
| PLEASE ADD IT TO THE INDEX AND REVISE THE FIXTURE AND |
| EQUIPMENT SCHEDULES ON THE PLAN TO MATCH THE SCHEDULES |
| ON P701- SECTION 107.2.1 WPB. |
| |
| 5) SHEETS A0.04 & P101: PLEASE PROVIDE THE CIVIL, PLANS |
| THAT ARE REFERENCED IN THE NOTES AND OTHER PLAN SHEET |
| NOTES FOR CONTINUATIONS OF THE PLUMBING AND STORM DRAIN |
| PIPING SYSTEMS- SECTION 107.2.1. |
| |
| 6) ELLIS AND GRITTER P101: REVISE THE GREASE WASTE |
| PIPING LAYOUT TO MATCH THE NEW LAYOUT SHOWN ON SHEETS |
| P401 & 501- SECTION 107.2.1 WPB. BOTH THE OLD AND NEW |
| P101 PLAN SHEETS AND P401 & P501 SHOW THE MOP SINK |
| DRAIN CONNECTING TO THE GREASE WASTE LINE, PLEASE NOTE |
| IN ACCORDANCE WITH SECTION 1003.3.1 FBC P THE MOP SINK |
| SHALL DRAIN INTO THE SANITARY AND NOT INTO THE GREASE |
| WASTE LINE. |
| |
| 7) P101 & P701 GREASE INTERCEPTOR: AS NOTED IN COMMENT |
| #1A A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE |
| GREASE INTERCEPTOR, AND THE SUBMITTAL SHALL INCLUDE THE |
| FOLLOWING LIST OF ITEMS. |
| |
| A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| MANUAL FOR THE SCHIER INTERCEPTOR WITH APPROVAL STAMPS |
| BY THE EOR. |
| |
| B) REVISED SIZING CALCULATIONS. PLEASE NOTE THE CURRENT |
| EQUIPMENT SCHEDULE SEEMS TO INDICATE TWO DIFFERENT |
| SIZING METHODS- THE PDI METHOD WHICH IS BASED ON GPM |
| FLOW-THRU RATINGS AND GREASE RETENTION TIME FOR THE |
| FIXTURES, AND FAC RULE 64E-6.013 METHOD WHICH IS BASED |
| ON THE NUMBER OF SEATS, GALLONS OF WASTEWATER ETC.- |
| THIS METHOD IS COMMONLY USED FOR GRAVITY-TYPE |
| INTERCEPTORS. |
| |
| 8) P101, P601. P701 SUMP PUMP AND PIT. |
| |
| A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE SUMP |
| PUMP. SECTION 712.3.1 FBC P. THE PUMP SHALL BE EQUIPPED |
| WITH AN OIL WATER SEPARATOR OR IT SHALL BE PROVIDED |
| SEPARATELY- SECTION 1003.4 FBC P. |
| |
| B) PROVIDE THE DIMENSIONS OF THE SUMP PIT IN THE |
| DETAIL- SECTION 712.3.2. |
| |
| C) PROVIDE A GAS TIGHT COVER FOR THE SUMP PIT- SECTION |
| 712.3.2. |
| |
| D) PROVIDE THE SIZE OF THE DISCHARGE PIPING AND PROVIDE |
| A VENT FOR THE PIT- SECTION 713.2.1. |
| |
| 9) P101 & P102: NOTE #8 (P102) INDICATES CLEANOUTS AT |
| THE BASE OF SANITARY STACKS WHICH ARE NOT SHOWN ON AT |
| THE CHASE LOCATION BY THE RESTROOMS. PLEASE NOTE THAT |
| SECTION 1101.8 REQUIRES STORM DRAIN CLEANOUTS TO BE |
| INSTALLED IN ACCORDANCE WITH THE CODES FOR SANITARY |
| DRAIN CLEANOUTS. |
| |
| 10) P103, NOTE 306: ACCORDING TO SECTION 1104.2 FBC P |
| FLOOR DRAINS SHALL NOT BE CONNECTED TO STORM DRAINS. |
| PLEASE PROVIDE MORE INFORMATION AND DETAILS TO CLARIFY- |
| SECTION 107.2.1 WPB. |
| |
| 11) P103: PROVIDE PRODUCT SUBMITTALS FOR RD-2, FD-1, |
| AND TD-1. PLEASE CLARIFY IF THE FD-1 AND TD-1 SHOWN IN |
| THE P701 SCHEDULE FOR THE INTERIOR ARE THE SAME TYPE OF |
| FIXTURES TO BE INSTALLED IN THE EXTERIOR OPEN ROOF |
| AREAS- SECTION 1105.1 FBC P AND SECTION 107.2.1 WPB. |
| |
| 12) P103: FD-1 ON THE LOWER ROOF SHALL NOT CONNECT TO |
| THE SANITARY PER SEC. 90-126 WPB CODE OF ORDINANCES. |
| |
| 13) P103 & P503: REFER TO SECTION 1107.1 FBC P AND |
| VERIFY THE ROOFS ARE DESIGNED FOR THE MAXIMUM POSSIBLE |
| DEPTH OF WATER THAT WILL POND THEREON AS DETERMINED BY |
| THE RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| SECTION 1106. |
| |
| 14) P103, P104 & P503: PROVIDE SECONDARY OR EMERGENCY |
| OVERFLOW ROOF DRAIN SYSTEMS INCLUDING CALCULATIONS AND |
| OVERFLOW DRAIN DETAILS- SEE SECTION 1108 FBC P. |
| |
| 15) P503: PROVIDE A CONDENSATE DISPOSAL RISER- SECTION |
| 107.2.1 WPB. |
| |
| 16) P401 SANITARY A: SEE COMMENT #7. |
| |
| 17) P401, SANITARY C: IT APPEARS A CLEANOUT IS MISSING |
| FOR THE 4 IN. GREASE WASTE BRANCH LINE IN THE KITCHEN |
| BY THE DISHWASHER- SECTION 708.1.4 FBC P. CLARIFY HOW |
| ACCESS TO THE WCO IN THE FREEZER WILL BE PROVIDED- |
| SECTIONS 708.1.9 & 708.1.0 FBC P. |
| |
| 18) P501, SANITARY D: PROVIDE CLEANOUTS AT THE BASES OF |
| THE 3 IN. STACKS. |
| |
| 19) P601: PLEASE PROVIDE INDIRECT WASTE PLUMBING PIPING |
| DETAILS FOR THE 2 AND 3-COMPARTMENT SINKS, THE |
| DISHWASHER, AND ALL OTHER DISHWASHING SINKS AND FOOD |
| HANDLING EQUIPMENT OR FIXTURES- REFER TO SECTIONS |
| 802.1, 802.1.1, 802.1.7, 802.1.8, AND 802.2 FBC P. |
| |
| 20) P701: THE 2 AND 3-COMPARTMENT SINKS APPEAR TO BE |
| MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| |
| 21) P701: ITEM #35 WHICH IS REFERENCED IN ITEM #36 & 37 |
| IS MISSING FROM THE SCHEDULE- SECTION 107.2.1 WPB. |
| |
| 22) P201: SHOW THE LOCATIONS OF THE WATER METER AND |
| MAIN SHUT OFF VALVES- SECTION 606.1 FBC P. |
| |
| 23) P201: SHOW FULL OPEN SHUT OFF VALVES FOR THE DOWN |
| FEEDING WATER SUPPLY LINES BY JAN. 118- SECTION |
| 606.1(5) FBC P. |
| |
| 24) P201: THERE APPEARS TO BE A SHUT OFF VALVE MISSING |
| AT THE RISER BY DOOR 108- SECTION 606.1(4) FBC P. |
| |
| 25) P-202, P403, P404 & P502: SHOW SHUTOFF VALVES FOR |
| THE RISERS UP TO THE HOSE BIBS, BAR AND BATHROOMS- |
| SECTION 606.1 FBC P. |
| |
| 26) P-201, P202, P203, P403, P404, & P502: SHOW THE |
| LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS, MIXING |
| VALVES, AND BACKFLOW PREVENTERS- SECTIONS 604.9, 416.4, |
| 607.1.2, & 608.3 FBC P. PLEASE NOTE THAT BACKFLOW |
| PREVENTERS ARE REQUIRED FOR WATER SUPPLY LINES TO THE |
| DISHWASHER, ICE MAKERS, WATER FILTERING SYSTEM, |
| CHEMICAL STORAGE CABINET, AND BEVERAGE AND COFFEE |
| DISPENSERS ETC. |
| |
| 27) P701: PLEASE LABEL THE LOCATION OF THE CHEMICAL |
| STORAGE CABINET ON THE DOMESTIC PLANS AND RISER |
| DRAWINGS- SECTION 608.3 FBC P. CLARIFY IF WASTE WATER |
| FROM THE CABINET WILL BE DRAINING INTO THE SANITARY |
| SYSTEM AND PROVIDE A NEUTRALIZING DEVICE IF APPLICABLE- |
| SECTION 803.1 FBC P. |
| |
| 28) P601: PLEASE PROVIDE A PLUMBING DIAGRAM FOR THE |
| CHEMICAL STORAGE CABINET- SECTION 107.2.1 WPB. |
| |
| 29) P701: PROVIDE THE EFFICIENCY RATINGS OF THE WATER |
| HEATERS IN THE SCHEDULE- TABLE C404.2 FBC EC. |
| |
| 30) P701: PROVIDE DRAIN PANS AND DRAIN PAN LINES FOR |
| THE WATER HEATERS- SECTIONS 504.7.1 & 504.7.2 FBC P. |
| |
| 31) P701: PROVIDE A PLUMBING DEVICE SCHEDULE SHOWING |
| THE MAKES AND MODEL NUMBERS AND LISTINGS OF THE WATER |
| HAMMER ARRESTORS, BACKFLOW PREVENTERS, MIXING VALVES, |
| AND TRAP PRIMERS- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |