2020-12-01 12:23:34 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| PERMIT- 20100465 |
| 12/1/2020 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) ACCORDING TO THE SUBMITTED SURVEY AND FLOOD MAPS THE |
| PROPOSED LOCATION OF 500-GALLON LP TANK APPEARS TO BE |
| LOCATED IN AN AE FLOOD ZONE. PLEASE PROVIDE COMPLETE |
| ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| 6.6.1.6. NFPA 58, AND SECTION R322.2.4 FBC RES. PLEASE |
| INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT SHOWS THE |
| BURIAL DEPTH, ANCHORING BASE MATERIAL, AND THE TYPES, |
| SIZES, AND NUMBERS OF ANCHORS, CABLES OR STRAPS, AND |
| THE TYPE OF PROTECTIVE SLEEVES FOR THE CABLES OR |
| STRAPS. |
| |
| 2) CORRECT THE NOTE ON SURVEY TO SHOW THE REQUIRED 10 |
| FT. CLEARANCE FOR THE GENERATOR EXHAUST TO THE WINDOW |
| AND DOORS OPENINGS- SECTION R303.5 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |