Plan Review Notes For Permit 20110581 |
Permit Number |
20110581 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-02-04 09:48:34 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | GENERATOR THAT WILL BE INSTALLED. FBC 107.2.1 | | | | 2) THE GENERATOR EXHAUST IS REQUIRED TO BE LOCATED 10 | | FEET FROM ANY OPENINGS INTO THE DETACHED GARAGE OR ANY | | OTHER BUILDINGS. FBC- R303.5.1 INTAKE OPENINGS. | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, | | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS | | AND LOADING DOCKS. THE BUILDING OFFICIAL HAS DETERMINED | | THAT THE REQUIREMENT FOR GENERATOR EXHAUST TO BE 10 | | FEET FROM ANY OPENINGS ALSO APPLIES TO DETACHED | | GARAGES. | | | | |
|