2021-02-04 09:48:34PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR THAT WILL BE INSTALLED. FBC 107.2.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE LOCATED 10
 FEET FROM ANY OPENINGS INTO THE DETACHED GARAGE OR ANY
 OTHER BUILDINGS. FBC- R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS. THE BUILDING OFFICIAL HAS DETERMINED
 THAT THE REQUIREMENT FOR GENERATOR EXHAUST TO BE 10
 FEET FROM ANY OPENINGS ALSO APPLIES TO DETACHED
 GARAGES.
  
  