Plan Review Notes
Plan Review Notes For Permit 20110569
Permit Number 20110569
Review Stop B
Sequence Number 1
Notes
Date Text
2020-12-15 07:54:33CAR CHARGING STATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 YOU ARE ADDING AN "ELEMENT" (CHARGING STATION) TO THE
 PARKING FACILITY WHICH YOU WILL NEED TO PROVIDE AN
 ACCESSIBLE ROUTE, CLEAR FLOOR SPACE AND REACH RANGES TO
 COMPLY WITH 2017 FBC ACCESSIBILITY - SEE CODE SECTIONS
 BELOW.
  
 106.1 ELEMENT. AN ARCHITECTURAL OR MECHANICAL COMPONENT
 OF A BUILDING, FACILITY, SPACE, OR SITE.
  
 201.4SCOPE OF COVERAGE.
 THIS CODE APPLIES TO FIXED OR BUILT-IN ELEMENTS OF
 BUILDINGS, STRUCTURES, SITE IMPROVEMENTS AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE. UNLESS
 SPECIFICALLY STATED OTHERWISE, ADVISORY NOTES, APPENDIX
 NOTES AND FIGURES CONTAINED IN THE CODE EXPLAIN OR
 ILLUSTRATE THE REQUIREMENTS; THEY DO NOT ESTABLISH
 ENFORCEABLE REQUIREMENTS.
  
 202.3ALTERATIONS.
 WHERE EXISTING ELEMENTS OR SPACES OR COMMON AREAS ARE
 ALTERED, EACH ALTERED ELEMENT, SPACE OR AREA SHALL
 COMPLY WITH THE APPLICABLE REQUIREMENTS OF CHAPTER 2
 AND SECTION 201.1.1. SEE SECTION 208.1 FOR EXISTING
 PARKING.
  
 206.2.2WITHIN A SITE.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT ACCESSIBLE
 BUILDINGS, ACCESSIBLE FACILITIES, ACCESSIBLE ELEMENTS,
 AND ACCESSIBLE SPACES THAT ARE ON THE SAME SITE.
  
 228DEPOSITORIES, VENDING MACHINES, CHANGE MACHINES,
 MAIL BOXES, AND FUEL DISPENSERS
 228.1 GENERAL.
 WHERE PROVIDED, AT LEAST ONE OF EACH TYPE OF
 DEPOSITORY, VENDING MACHINE, CHANGE MACHINE, AND FUEL
 DISPENSER SHALL COMPLY WITH 309.
  
 309 OPERABLE PARTS
  
 309.1GENERAL.
 OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 EXCEPTION: GAS PUMP NOZZLES SHALL NOT BE REQUIRED TO
 PROVIDE OPERABLE PARTS THAT HAVE AN ACTIVATING FORCE OF
 5 POUNDS (22.2 N) MAXIMUM.
  
 DRAWING C3-00 SHOWS CODE VERSION (IBC) NEEDS TO SHOW
 2017 FBC
  