Plan Review Notes For Permit 20110544 |
Permit Number |
20110544 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-17 10:04:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE DOES NOT APPEAR TO BE INDICATIONS OF THE BELOW | | REQUIRED FEATURES. | | | | | | NFPA 1, 11.9 | | | | H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF | | THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL | | | | N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND | | TRANSFER FEATURES. | | | | NFPA 101 11.8.6 | | | | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS | | | | PLEASE REVIEW AND PROVIDE DETAILS. | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|