2020-11-30 17:24:411ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20110528
 11/30/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: THE DRAINAGE FROM THE CHILLER SHALL NOT
 BE DISCHARGED INTO THE PLUMBING SYSTEM WITHOUT BEING
 THOROUGHLY DILUTED, NEUTRALIZED OR TREATED BY PASSING
 THROUGH AN APPROVED DILUTION OR NEUTRALIZING DEVICE-
 SEE SECTION 803.1 FBC P.
  
 2) P1.1: PROVIDE A BACKFLOW PREVENTER FOR THE WATER
 SUPPLY LINE TO THE CHILLER- SECTIONS 608.3 FBC P.
  
 3) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  