Plan Review Notes
Plan Review Notes For Permit 20110528
Permit Number 20110528
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-04 12:20:17 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF ADDITIONAL ELECTRICAL WORK NOT SHOWN ON
 REVISION APPLICATION.
  
 2) YOU SHOW 2 MAINS OF THREE IS THE OTHER LOCATED IN
 SAME ROOM AS OTHRS? 230.71
  
 3) FPL CT CAN IS NOT USED FOR SPLICING OF CONDUCTORS,
 CONDUCTORS ARE TO BE CONTINUOUS THROUGH THE CT CAN. YOU
 MAY SET A GUTTER AFTER THE CT CAN FOR SLICING.