2020-12-04 12:20:17 | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) VALUE OF ADDITIONAL ELECTRICAL WORK NOT SHOWN ON | | REVISION APPLICATION. | | | | 2) YOU SHOW 2 MAINS OF THREE IS THE OTHER LOCATED IN | | SAME ROOM AS OTHRS? 230.71 | | | | 3) FPL CT CAN IS NOT USED FOR SPLICING OF CONDUCTORS, | | CONDUCTORS ARE TO BE CONTINUOUS THROUGH THE CT CAN. YOU | | MAY SET A GUTTER AFTER THE CT CAN FOR SLICING. |
|