Plan Review Notes For Permit 20110522 |
Permit Number |
20110522 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-01-22 15:19:18 | FAILED | | | | 1) ELECTRICAL NOTE #2 (PROVIDED 4 TIMES) CALLS OUT A | | WEATHERPROOF J-BOX AND 3/4 INCH CONDUIT WITH PULLWIRE | | STUBBED INTO ACCESSIBLE TENANTS CEILING ARE FOR | | EXTERIOR SIGNAGE. PROVIDE A DETAIL FOR EACH DIFFERENT | | LOCATION SO THAT STAFF CAN VERIFY THAT THIS ELECTRICAL | | CONNECTION COMPLIES WITH THE ROSEMARY SQUARE TENANT | | SIGN CRITERIA REQUIREMENT THAT ALL LIGHTING CONDUIT, | | WIRING, BALLAST BOXES, TRANSFORMERS, AND OTHER | | EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL BE | | CONCEALED AND NOT VISIBLE TO THE PUBLIC. ***** THE | | COMMENT RESPONSE DOES NOT ADDRESS/VERIFY THAT THE ITEMS | | BEING INSTALLED AS PART OF THE LANDLORD WORK ARE NOT | | VISIBLE FROM THE PUBLIC. ONCE THIS IS VERIFIED, THEN | | STAFF WILL DEAL WITH THE SIGNAGE CONTRACTOR ON THE | | SIGNAGE CONNECTIONS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | | | |
|