2020-12-16 13:48:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20110495 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PROJECT SUMMARY FOR THE ENERGY CALCULATIONS HAS |
| A TOTAL CONDITIONED AREA IS 110 SF. SHEET A0.03 |
| INDICATES THE AREA OF WORK IS 4226 SF. PLEASE PROVIDE A |
| PROJECT SUMMARY FOR THE MECHANICAL SIZING CALCULATIONS |
| BASED ON THE SF INDICATED ON SHEET A0.03. FBC 107.2.1 |
| |
| 2) SHEET M6.1: OUTDOOR AIR CALCULATIONS DO NOT MATCH |
| TABLE 403.3.1.1. THE OFFICE SPACES ARE CALCULATED AT |
| #/1000SQ.FT ( 4226\1000= 4.226 X 5 OCC. DENSITY = 21.13 |
| + 4226X.06= 253.56) |
| 21.13 + 253.56 = 274.69 CFM OF OUTDOOR AIR REQUIRED. |
| FBC M TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |