2020-11-17 07:03:53 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT-20110495 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE MECHANICAL EQUIPMENT HEATING AND |
| COOLING SIZING. FBC EC C403.2.1 |
| |
| 2) THE SQUARE FOOTAGE IS OFF ON SHEETS A0.03 AND M6.1. |
| PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON THE |
| ARCHITECTURAL SQUARE FOOTAGE AND THE OCCUPANT LOAD |
| BASED ON THAT. FBC M 403.3.1.1 |
| |
| 3) PLEASE SHOW FIRE DAMPERS FOR THE RATED WALL |
| PENETRATIONS OF THE EXISTING DUCTWORK. FBC M 607.5 |
| |
| 4) SHEET A0.03 INDICATES RATED WALLS AT ROOMS- O.FILES, |
| S STORAGE AND WAITING. PLEASE SHOW FIRE DAMPERS AT EACH |
| LOCATION THAT DUCT WORK PENETRATES THESE WALLS. FBC M |
| 607.5 |
| |
| 5) PLEASE SHOW FIRE DAMPERS IN ALL LOCATIONS WHERE THE |
| DUCTWORK PENETRATES A RATED WALL. FBC M 607.5 |
| |
| 6) PROVIDE A MECHANICAL DEMO SHEET THAT INCLUDES THE |
| EXISTING DUCTWORK SIZES. FBC 107.2 |
| |
| 7) AREA ABOVE CEILING IS CONSIDERED A PLENUM, PLEASES |
| MAKE SURE ALL TRADES ARE AWARE. FBC M 602.2.1MATERIALS |
| WITHIN PLENUMS. |
| EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH |
| 602.2.1.7, MATERIALS WITHIN PLENUMS SHALL BE |
| NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING |
| A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |