Plan Review Notes
Plan Review Notes For Permit 20110495
Permit Number 20110495
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-17 07:03:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20110495
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT HEATING AND
 COOLING SIZING. FBC EC C403.2.1
  
 2) THE SQUARE FOOTAGE IS OFF ON SHEETS A0.03 AND M6.1.
 PLEASE PROVIDE AN OUTDOOR AIR CALCULATION BASED ON THE
 ARCHITECTURAL SQUARE FOOTAGE AND THE OCCUPANT LOAD
 BASED ON THAT. FBC M 403.3.1.1
  
 3) PLEASE SHOW FIRE DAMPERS FOR THE RATED WALL
 PENETRATIONS OF THE EXISTING DUCTWORK. FBC M 607.5
  
 4) SHEET A0.03 INDICATES RATED WALLS AT ROOMS- O.FILES,
 S STORAGE AND WAITING. PLEASE SHOW FIRE DAMPERS AT EACH
 LOCATION THAT DUCT WORK PENETRATES THESE WALLS. FBC M
 607.5
  
 5) PLEASE SHOW FIRE DAMPERS IN ALL LOCATIONS WHERE THE
 DUCTWORK PENETRATES A RATED WALL. FBC M 607.5
  
 6) PROVIDE A MECHANICAL DEMO SHEET THAT INCLUDES THE
 EXISTING DUCTWORK SIZES. FBC 107.2
  
 7) AREA ABOVE CEILING IS CONSIDERED A PLENUM, PLEASES
 MAKE SURE ALL TRADES ARE AWARE. FBC M 602.2.1MATERIALS
 WITHIN PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.7, MATERIALS WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL BE LISTED AND LABELED AS HAVING
 A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  