Notes |
Date |
Text |
2020-11-19 16:06:25 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT THE REQUIRED TEST REPORTS FOR THE CORK SOUND | | INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED | | FOR THE APPLICABLE CONSTRUCTION CONDITIONS. | | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | E 90. | | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | |
|