Plan Review Notes For Permit 20110462 |
Permit Number |
20110462 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-20 15:11:11 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | PROVIDE A RISER DIAGRAM SHOWING MAINS FOR THIS AND MAIN | | HOUSE. 230.71 215.5 | | | | PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A | | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH | | CIRCUIT. NEC 250.32; FBC RE3607.3 | | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | R314.3, FBC 107.2.1 |
|