2020-11-25 09:09:511ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20110461
 11/25/20
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1A/B SANITARY RISER:
  
 A) THE WET VENTING SYSTEMS FOR THE GUEST HOUSE BATH AND
 BATHS 2 & 3 ARE NOT IN COMPLIANCE WITH SECTION
 P3108.2.1- NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION.
  
 B) WASHER: SHOW A 2 IN. FIXTURE DRAIN CONNECTING TO A 3
 IN. VERTICAL STACK- SECTION 406.2 FBC P.
  
 2) SHOW THE LOCATIONS OF THE WASHER SHUT OFF VALVES AND
 INDICATE THAT THEY WILL BE ACCESSIBLE PER SECTION
 P2903.9.3 FBC RES.
  
 3) WATER HEATER: THE ENERGY FORM R405-2017 INDICATES A
 40-GALLON NATURAL GAS WATER HEATER. SHOW THE LOCATION
 OF THE WATER HEATER ON THE PLAN, PROVIDE AN EQUIPMENT
 SCHEDULE AND SUBMIT MANUFACTURER'S SPECIFICATIONS-
 SECTION G2448.1 FBC RES. PLEASE NOTE A SEPARATE PERMIT
 AND PLANS ARE REQUIRED FOR THE GAS PIPING TO THE WATER
 HEATER AND ALL OTHER GAS FIRED APPLIANCES AND
 EQUIPMENT- SECTIONS 105.1 AND 107.2.1 WPB. THE GAS
 PLANS SHALL INCLUDE COMBUSTION AIR CALCULATIONS AND
 VENTING PLANS FOR ALL GAS-FIRED APPLIANCES.
  
 4) PROVIDE A WATER RISER- SECTION 107.3.5.3 WPB.
  
 5) PROVIDE SHOWER PAN DETAILS- SECTION P2709.2 FBC RES.
  
 6) BACKFLOW PREVENTER FOR POTABLE WATER SERVICE: PLEASE
 NOTE A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC,
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT. AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  