Plan Review Notes
Plan Review Notes For Permit 20110461
Permit Number 20110461
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-30 13:47:57CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: FAILED.
  
 1) PLEASE SUBMIT ELECTRICAL DRAWINGS FOR GUEST HOUSE
 FBC 107
 2) PLEASE SPECIFY GROUNDING ELECTRODE SYSTEM FOR BOTH
 HOUSE AND GUEST HOUSE NEC 250
 3) GROUNDING CONDUCTOR (BONDING JUMPER) FROM METER TO
 PANEL A SHOULD BE # 4 CU IF SERVICE ENTRANCE CONDUCTORS
 ARE #3/0. NEC 250-102
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved