Plan Review Notes For Permit 20110461 |
Permit Number |
20110461 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-11-30 13:47:57 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | ELECTRICAL REVIEW STATUS: FAILED. | | | | 1) PLEASE SUBMIT ELECTRICAL DRAWINGS FOR GUEST HOUSE | | FBC 107 | | 2) PLEASE SPECIFY GROUNDING ELECTRODE SYSTEM FOR BOTH | | HOUSE AND GUEST HOUSE NEC 250 | | 3) GROUNDING CONDUCTOR (BONDING JUMPER) FROM METER TO | | PANEL A SHOULD BE # 4 CU IF SERVICE ENTRANCE CONDUCTORS | | ARE #3/0. NEC 250-102 | | | | END OF COMMENTS. | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|