 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PRE-CAST GENERATOR PAD ENGINEERING
  
 1.PROVIDE SITE SPECIFIC WIND LOAD DESIGN PRESSURE
 CALCULATIONS FOR USE WITH THIS SYSTEM. (SEE EOR NOTE)
 SITE SPECIFIC LOAD REQUIREMENTS SHALL BE LESS THAN OR
 EQUAL TO THE POSITIVE OR NEGATIVE DESIGN PRESSURE
 CAPACITY LISTED
 IN THE CONCRETE PAD SCHEDULE.
  
 FBC 107.3.5.1.1(8) PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16
 1603.1.4 WIND DESIGN DATA.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  